LEGRAND Wattstopper FSP-301B Instrucciones De Instalación página 3

Sensor pir de bajo voltaje para luminarias de exterior, tipo ip66 con función de atenuación continua y con bluetooth de bajo consumo
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Ground
(Green)
Non-Dimming
Ballast/Driver
Dim– (Gray)
Dim+ (Violet)
+VDC (Red)
Ground (Green)
Dim-to-Off
Ballast/Driver
Dim– (Gray)
(Blue)
+VDC Output (Red)
COM/GND (Black)
Dim+ (Violet)
NAVIGATION
Navigation is achieved by selecting any of the desired parameters.
Settings can be changed via number of inputs or sliders.
NOTE: When you change parameter
values on the FSP-301B, you
need to wait about 3 minutes
before the new parameters
are saved into the memory.
Neutral
(White)
Line (Black)
CTRL (Blue)
BZ-200 Power Pack
120 – 277 VAC (1 φ ), 50/60 Hz
20A Ballast/ELV/MLV/Tungsten/LED
LISTED
16A E-Ballast/CFL
Appliance
1HP @ 120/240VAC
Control
88T9
20A 120VAC Plug Load – Receptacle
Class 2 Output
White
Power Pack
Red
Lighting
Neut.
24 VDC, 225 mA
Switch
Load
Black
Red
Hot
Green
UL 2043 Plenum Rated
Ground
Control
Common
Any 3-Wire
24VDC
+24VDC
Sensor
www.legrand.us • 800.879.8585
Class 2
16094r1
wiring only
COM (Black)
Line (Black)
Neutral (White)
Wiring with an
external DC
power supply
WIRING
Dimming
Ballast/Driver
Dim– (Gray)
Dim+ (Violet)
FSP-301B CONFIGURATION WITH THE
SENSOR CONFIG APP
The Sensor Configuration App is available
®
for both iOS
and Android
"Wattstopper Sensor Config" on your device
to download.
NOTE: Bluetooth communication ranges can
vary depending on the device, as well
as mobile carrier. Wattstopper recommends devices with
Bluetooth 5.0. Iphone 8 and Samsung Galaxy S8 and
later devices are recommended for optimal performance.
The Sensor Configuration tool is a
mobile app for changing defaults
and testing of the FSP-301B. It
provides wireless access to the
FSP-301B sensors for parameter
changes and testing. Within a
certain mounting height of the
sensor, the Sensor Configuration
app allows modification of the
system without requiring ladders
or tools. If no configuration steps
are taken, the sensor will use its
default parameter values.
The Sensor Configuration app
display shows menus and prompts
to lead you through each process.
The mobile app provides a simple
way to navigate through the customization fields.
The Sensor Configuration app allows bi-directional communication
between the FSP-301B and the mobile app. Simple menu screens
let you see the current status of the sensor and make changes.
It can change FSP-301B sensor parameters such as high/low
mode, sensitivity, time delay, cut off and more. With the Sensor
Configuration app you can also establish and store FSP-301B
parameter profiles and enable continuous dimming.
The Sensor Configuration mobile app has the ability to detect
multiple sensors based on signal strength or distance.Every
time the commissioning tool establishes communication with
the FSP-301B, the controlled load will flash, providing a visual
indication of which FSP-301B you are configuring.
For details on the features and operation, download the Config
App User Guide from the wattstopper web site at :
https://www.legrand.us/wattstopper.aspx
NOTE: The Bluetooth low energy technology radio stops
broadcasting after 7 days of being powered on if no
password is set for the device. Cycling the power turns
the Bluetooth radio back on.
3
Ground
Neutral
(Green)
(White)
Line (Black)
CTRL (Blue)
BZ-200 Power Pack
120 – 277 VAC (1 φ ), 50/60 Hz
20A Ballast/ELV/MLV/Tungsten/LED
LISTED
16A E-Ballast/CFL
Appliance
1HP @ 120/240VAC
Control
88T9
20A 120VAC Plug Load – Receptacle
Class 2 Output
White
Power Pack
Red
Lighting
Neut.
24 VDC, 225 mA
Switch
Load
Black
Red
Hot
Green
UL 2043 Plenum Rated
Ground
Control
Common
Any 3-Wire
24VDC
+24VDC
Sensor
www.legrand.us • 800.879.8585
Class 2
16094r1
wiring only
COM (Black)
+VDC (Red)
®
devices. Search

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Wattstopper fsp-301b-sWattstopper fsp-301b-d

Tabla de contenido