Victron energy MultiPlus 1600VA Serie Manual página 18

Ocultar thumbs Ver también para MultiPlus 1600VA Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 89
5.4.1. DIP switch 1 to 3
These DIP switches can be used to set:
- Battery charge voltage and Absorption time
- Search mode
Ds1-ds2: Setting the charge algorithm
Absorption
Ds1-ds2
voltage
Ds1=off
14.4
Ds2=off
28.8
(default)
57.6
Ds1=on
14.1
Ds2=off
28.2
56.4
Ds1=off
14.7
Ds2=on
29.4
58.8
Ds1=on
15.0
Ds2=on
30.0
60.0
DS3 double function.
Ds3: Search Mode and store
Store the settings by toggling DIP switch 3 one time.
16
Float
Storage
voltage
Voltage
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
off = off
Absorption
Time
Suitable for
(hours)
Gel Victron Deep
Discharge
8
Gel Exide A200
AGM Victron Deep
Discharge
Gel Victron Long
Life (OPzV)
Gel Exide A600
8
(OPzV)
Gel MK battery
Li-ion (LiFePO4)
AGM Victron Deep
Discharge
Tubular plate or
5
OPzS batteries in
semi-float mode
AGM spiral cell
Tubular plate or
6
OPzS batteries in
cyclic mode
on = on

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Multiplus 12/1600/70Multiplus 24/1600/40Multiplus 48/1600/20

Tabla de contenido