Modbus Settings (2001; Values Register (1001 - CS Instruments VA 570 Manual De Instrucciones

Tabla de contenido

Publicidad

Operation
8.3.2.1
Modbus Settings
Modbu
Modbu
s
s
No.of
Registe
Addres
Byte
r
s
2001
2000
2
2002
2001
2
2003
2002
2
2004
2003
2
2005
2004
2
8.3.2.2

Values Register (1001 ...1500)

Modbu
Modbu
s
s
No.of
Registe
Addres
Byte
r
s
1101
1100
4
1109
1108
4
1117
1116
4
1125
1124
4
1133
1132
4
1141
1140
4
1149
1148
4
1157
1156
4
1165
1164
4
1173
1172
4
1181
1180
4
1189
1188
4
1197
1196
4
1205
1204
4
1213
1212
4
1221
1220
4
VA 570 Español V1.05
(2001...2005)
Data
Description
Type
UInt16
Modbus ID
UInt16
Baudrate
UInt16
Parity
UInt16
Number of Stopbits
UInt16
Word Order
Data
Description
Type
Flow in m³/h
Float
Flow in Nm³/h
Float
Flow in m³/min
Float
Flow in Nm³/min
Float
Flow in ltr/h
Float
Flow in Nltr/h
Float
Flow in ltr/min
Float
Flow in Nltr/min
Float
Flow in ltr/s
Float
Flow in Nltr/s
Float
Flow in cfm
Float
Flow in Ncfm
Float
Flow in kg/h
Float
Flow in kg/min
Float
Flow in kg/s
Float
Flow in kW
Float
Default
Read
Setting
Write
1
R/W
4
R/W
1
R/W
R/W
0xABCD
R/W
Rea
Def
d
aul
Writ
t
e
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Unit /Comment
Modbus ID 1...247
0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38400
0 = none
1 = even
2 = odd
0 = 1 Stop Bit
1 = 2 Stop Bit
0xABCD = Big Endian
0xCDAB = Middle Endian
Unit /Comment
Page 24 of 33

Publicidad

Tabla de contenido
loading

Productos relacionados para CS Instruments VA 570

Tabla de contenido