Typical Inlet Pipe Diameters
Use 3/8" black iron pipe or greater. Installa-
tion must include an equipment shutoff valve,
union, and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from heater (see
Figure 12).
IMPORTANT: Install an equipment shutoff
valve in an accessible location. The equip-
ment shutoff valve is for turning on or shutting
off the gas to the appliance.
For propane/LP installations, apply pipe
joint sealant lightly to male threads. This will
prevent excess sealant from going into pipe.
Excess sealant in pipe could result in clogged
heater valves.
The installer must supply an external regula-
tor. The external regulator will reduce incom-
ing gas pressure. You must reduce incoming
gas pressure to between 11" WC and 14" WC.
Ground
Joint Union
Tee Joint
Reducer
Bushing to
Test Gauge
1/8" NPT
Connection*
1/8" NPT
Plug Tap
Tee Joint
Sediment
Pipe Nipple
Trap
Gap
Figure 12 - Gas Connection
* Purchase the optional CSA design-certified equipment
shutoff valve from your dealer.
200132-01A
INSTALLATION
If you do not reduce incoming gas pressure,
heater regulator damage could occur. Install
external regulator with the vent pointing down
as shown in Figure 13. Pointing the vent down
protects it from freezing rain or sleet.
Install sediment trap in supply line as shown
in Figure 12. Place sediment trap where it is
within reach for cleaning. Place sediment trap
where trapped matter is not likely to freeze.
A sediment trap traps moisture and contami-
nants. This keeps them from going into heater
controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
WARNING: Test all gas piping
and connections for leaks after
installing or servicing. Correct
all leaks at once (see page 16).
3/8" NPT
Pipe Nipple
Equipment
Shutoff Valve
Natural Gas
From Gas Meter
(5" W.C.** to
9" W.C.
Pressure)
Propane/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
3" Minimum
Pressure)
www.usaprocom.com
External
Regulator with
Propane/LP
Vent Pointing
Supply Tank
Down
Figure 13 - External Regulator
with Vent Pointing Down
15