8 . B A T T E R Y
The battery is the only UPS component which is not in permanent use. It has a useful life of
approximately 3 to 5 years. However, frequent major discharges or exposure to
temperatures over 20°C will shorten its life span. We therefore recommend that users
recharge the battery once every 3 months when the unit is not in use in order to compensate
for natural discharging. UPS backup time will depend on the powered load, as well as the
age and condition of the batteries.
WARNING!
Batteries should always be replaced by qualified technicians. Batteries have a very high
short circuit current: connection errors could cause electric arcs resulting in
serious burns.
9 . T R O U B L E S H O O T I N G
Should the UPS fail to function correctly we recommend you perform the following tests
before calling the Hot Line.
Check list:
• Is the main switch in the "ON" position?
• Is the UPS plugged into the mains power supply?
• Does the power supply fall within specified unit values?
• Is the UPS overloaded?
• Is the battery flat or defective?
PROBLEM
No LED display on
front panel.
Alarm continuously
sounding when mains
is normal.
In the event of power
failure, backup time is
shortened.
Mains normal but the
unit is on battery mode
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 03 11 AA 59 201 02
POSSIBLE CAUSE
Low battery
Faulty battery.
UPS is not turned on.
UPS overload.
UPS fault
UPS overload.
Battery voltage too low.
Battery defect due to high
temperature operating
environment, or improper
use of battery.
Loose power cord.
Thermic fuse
SOLUTIONS
Charge battery for up to 8 hours.
Replace with the same type of battery.
Press the power switch again to turn on
the UPS.
Check that the load matches the UPS
capability stipulated in the specifications.
Return the unit to service center
Remove some non-critical load.
Charge battery at least 8 hours.
Replace with the same type of battery.
Connect the power cord properly.
Press the thermic fuse
7