Installing the Drain Pipe
3-5-2.
CAUTION
(1) How to Connect Drain Port and Drain Hose
First insert the supplied hose band into the drain port
pipe. Then make sure the head of the screw is facing
toward a technical engineer when placing the screw of
the hose band at an upward angle.
Insert the soft PVC socket of the supplied drain hose to
the drain port pipe.
Never apply the adhesive to the soft PVC socket
side.
Insert the drain hose to the point where there is a
difference in level as shown in the figure below and fasten
it with the hose band 5 mm away from that position.
Tightening torque must be 2.5 ~ 3.4 N·m.
· Tightening position of the hose band must be upward.
Drain port
(Drainage check section
on drain port, transparent)
Indoor
unit
* Drain port may possibly
be damaged and cause
the water leakage if
PVC adhesive is used.
Do not use adhesive here.
Fasten the hose band as shown the diagram
below. (Torque: 2.5 N·m - 3.4 N·m)
Indoor
unit
Uneven surface
* After checking the drainage, wrap the supplied packing and drain pipe insulator around the pipe.
Hose band (supplied)
Uneven
Soft PVC socket
surface
Drain hose
(supplied)
Packing
5 mm
(supplied)
(2) How to Install the Drain Pipe
Connect the hard PVC pipe joint (VP25: field supply) to
the side of the hard PVC socket of the drain hose.
Apply approx. 2 g of adhesive on the side of the hard PVC
socket of the drain hose and the side of the hard PVC
pipe joint.
Do not apply force to the drain port when connecting the
drain pipe. Install and fix it near the indoor unit as close
as possible.
Hard PVC pipe joint
Hard PVC socket
(VP25 field supplied)
* Apply approx. 2 g of adhesive on the side of
the hard PVC socket of the drain hose and
the side of the hard PVC pipe joint.
Wipe off the protrusion-adhesive with a soft
cloth.
Adhere with PVC adhesive.
57 mm
20 mm or more
Note:
Be sure to tightly insert the hard PVC pipe joint
(including elbow) minimum 20 mm or more.
* However, do not use the hard PVC
pipe joint allowable more than 55 mm
Drain insulator
insertion.
(supplied)