Regulation Logic; On-Off Managment; Cooling / Heating Mode Changeover; Mixing Chamber - LMF Clima LCM Manual De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

6.1. On-Off managment

The unit can be turned On-Off in the following way:
Off by digital input, main priority
Off by Remote keyboard:
1) While weekly program is not active, the unit is definitively On/Off
2) While weekly program is active, the unit can be temporarily turned On/Off till next event (in case of this the
active profile led blinks)
The set point is the same of the last time range.
In case of blackout the unit restarts with the time range status
Off by BMS via MODBUS
Off by weekly program

6.2. Cooling / heating mode changeover

Cooling / heating mode can be switched by:
Digital input (  / / = 2)
Remote Keyboard
BMS via MODBUS
Automatically with exhaust air sensor (  / / = 1)
Heating
Set winter
Automatically with fresh air sensor (  / / = 0)
If Te <  = Heating mode
If Te > + = Cooling mode

(password) 1


Fresh air temperature set point for automatic changeover

Season changeover differential

6.3. Mixing chamber

When a mixing box is present on the unit it is necessary to enable the parameter
be activated in the following cases.
During winter start-up for a set period (Parameter

6.4. Water coil antifreeze

Alarm and error active only in heating mode, if electric preheater is installed on the unit it is activate for a set period
to try to increase the temperature before entering in alarm condition.
When the antifreeze alarm is active the fans are Off, the dampers closed, the valve opened and the pumps are active.
In case of antifreeze sensor fault:
When the unit is in stan-by the valves opens in the fresh air temperature is lower than antifreeze set point
When the unit is On the antifreeze is managed using the supply air temperature
firmware 0.06
Electronic Control "LCM" User Manual

6 Regulation Logic

Cooling
exhaust air sensor
Set summer
Heating
Te = fresh air sensor



15.0°C
10.0°C
)
Rev.02
Cooling
Te

; recirculation of return air will
EN
EN 9/ 15

Publicidad

Tabla de contenido
loading

Productos relacionados para LMF Clima LCM

Tabla de contenido