CLE INSTALLATION
INSTRUCTIONS
Product Safety
This product must be installed in accordance with the applicable
!
installation codes by a person familiar with the construction and
operation of the product and the hazards involved.
To avoid risk of electrical shock, disconnect power before
installing, wiring, or servicing the fixture.
The light source contained in this luminaire shall only be replaced
by the manufacturer or his service agent or similarly qualified
person.
Do not apply paint, lubricants or other coatings to fixture,
!
suspension cables, or fasteners.
If you attach a safety cable, attach it to the fixture in accordance
!
with all national, state, and local construction codes.
See illustrations on page 1.
1: Verify Optic Type
Use the optic type specified in the project plan — WIDE, AISLE,
or DIFFUSE. The optic type is printed on the serial number label.
2: Add Tracking Labels to Sticker Book
Detach plastic bag from fixture, then remove barcode label from bag and
affix to sticker book depicting the intended installation location of the
fixture.
3: Install Fixtures
Option 1: Rigid Mount
a. Refer to the sticker book to confirm the correct location and
orientation of the fixture.
b. Install the rigid mount to one of the following: a surface using 1/4
in (6 mm) fasteners, a 3/4 in (21 mm) trade size pendant, or a 4 in
(10 cm) square or octagonal junction box.
c. Install the fixture by lifting vertically. Ensure that all four tabs are
fully engaged in the fixture.
d. Use the provided locking screws to lock the fixture to the brackets.
Tighten all locking screws to 20 in-lbs (2.3 N-m).
Option 2: Aircraft Cable
a. Refer to the sticker book to confirm the correct location and
orientation of the fixture.
b. Secure aircraft cable to a beam or truss.
c. Connect cable to short edge of fixture using aircraft cable
hanging hardware.
d. Use a level to level the fixture.
2
Read these instructions before using product.
!
Do not use fixture if the housing, aircraft cables, optics, or power
!
cable are damaged.
Do not touch optical lenses with your fingers or hands. In the
!
event you need to clean the lens, use a damp cloth and gently
swab the affected area.
Only handle fixture by sheet metal surfaces. Do not grasp or
!
handle by the fixture lenses.
Maximum current for looping-in connections in wiring
compartment is 10A.
Suitable for indoor use.
!
4: Make Electrical Connections
Do not connect or disconnect while under load.
a. Remove the screw retaining the wiring compartment access panel.
b. Make the appropriate knockout in the wiring compartment
access panel.
c. Identify the power lines that will attach to facility mains power.
d. Install appropriate strain relief in wiring compartment
access panel.
e. Feed wires through the knockout and strain relief.
f. Insert wires into appropriate connectors. For IEC fixtures, WAGO
221 connectors must be used. If WAGO
ensure wires are stripped to 0.43 in (11 mm).
g. In accordance with national, state, and local electrical codes,
connect to facility mains power.
h. Replace wiring compartment access panel and tighten screw to
20 in-lbs (2.3 N-m).
5: Verify Sticker Book
To prevent issues during commissioning, ensure that the placement
of the bar code label in the sticker book corresponds to the fixture's
physical location in the facility.
Product Ratings
!
CLE-B1-ST: 120-277 V AC, 50/60 Hz, 80 W (max), 0.67 A (max)
CLE-D1-ST: 120-277 V AC, 50/60 Hz, 117 W (max), 1.0 A (max)
CLE-F1-ST: 120-277 V AC, 50/60 Hz, 156 W (max), 1.35 A (max)
CLE-B1-CE: 220-240 V~, 80 W, 50-60 Hz
CLE-D1-CE: 220-240 V~, 117 W, 50-60 Hz
CLE-F1-CE: 220-240 V~, 156 W, 50-60 Hz
CLE-B1-HV: 347-480 V~, .26 A, 50-60 Hz
CLE-D1-HV: 347-480 V~, .37 A, 50-60 Hz
CLE-F1-HV: 347-480 V~, .47 A, 50-60 Hz
ENGLISH
®
221 connectors are used,
®