► To set the external static pressure from the function selection screen on the remote controller
Follow the instructions below and the instructions detailed in the remote controller manual for how to set the switches.
1. Set the function setting No. 32 (Switch setting/Function selection) to "2".
2. Set the function setting No. 8 and No. 10 to appropriate values, according to the external static pressure.
Function setting No.
Selection
No. 32
Switch setting
1
Function selection
2
9.6. Setting addresses
(Be sure to operate with the main power turned OFF.)
[Fig. 9.5.1] (P.6)
<Indoor controller board>
•
There are two types of rotary switch setting available: setting addresses 1 to 9
and over 10, and setting branch numbers.
1 How to set addresses
Example: If Address is "3", remain SW12 (for over 10) at "0", and match
SW11(for 1 to 9) with "3".
2 How to set branch numbers SW14 (Series R2 only)
The branch number assigned to each indoor unit is the port number of the
BC controller to which the indoor unit is connected.
Leave it to "0" on the non-R2 series of units.
•
The rotary switches are all set to "0" when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
•
The determination of indoor unit addresses varies with the system at site. Set
them referring to the Data Book.
9.9. Electrical characteristics
Model
PEFY-P06NMAU-E4
PEFY-P08NMAU-E4
PEFY-P12NMAU-E4
PEFY-P15NMAU-E4
PEFY-P18NMAU-E4
PEFY-P24NMAU-E4
60 Hz
PEFY-P27NMAU-E4
PEFY-P30NMAU-E4
PEFY-P36NMAU-E4
PEFY-P48NMAU-E4
PEFY-P54NMAU-E4
16
Initial
Current
External static
setting
setting
pressure
○
0.14 in. WG
(35 Pa)
0.20 in. WG
(50 Pa)
0.28 in. WG
(70 Pa)
0.4 in. WG
(100 Pa)
0.60 in. WG
(150 Pa)
Symbols : MCA : Max. Circuit Amps ( = 1.25 × FLA) FLA : Full Load Amps
IFM : Indoor Fan Motor
Indoor Unit
Hz
Volts
Voltage range
208–230 V
188 to 253 V
Function
setting No.
Initial setting
No. 8
No. 10
2
1
3
1
○
1
2
2
2
3
2
9.7. Sensing room temperature with the built-
in sensor in a remote controller
If you want to sense room temperature with the built-in sensor in a remote controller,
set SW1-1 on the control board to "ON". The setting of SW1-7 and SW1-8 as
necessary also makes it possible to adjust the air flow at a time when the heating
thermometer is OFF.
9.8. Changing the power voltage setting
(Be sure to operate with the main power turned OFF.)
[Fig. 9.5.1] (P.6)
Please set the switch SW21 according to the power voltage.
•
Set SW21-6 to OFF side when the power supply is 230 volts.
•
When the power supply is 208 volts, set SW21-6 to ON side.
Output : Fan motor rated output
IFM
MCA (A)
Output (kW)
1.75
0.085
1.75
0.085
2.13
0.085
2.88
0.121
2.94
0.121
2.88
0.121
2.88
0.121
2.88
0.121
4.25
0.300
4.38
0.300
4.38
0.300
[Important]
Current
Be sure to write down the settings
setting
for all functions in the "Current
setting" row if any of the initial
settings has been changed.
FLA (A)
1.40
1.40
1.70
2.30
2.35
2.30
2.30
2.30
3.40
3.50
3.50