INSTALLATION AND OPERATION
•
Plug in devices only so that a total current of 16A is not exceeded.
•
The socket outlet is reconnectable. Before opening the socket, disconnect
its power supply.
•
When changing the connected cable, use the following type of cable:
H07RN-F 3G1.5 for cable lengths of 5.0 m.
•
Connect the green-yellow protective conductor correctly at the
connection point with the protective conductor mark.
•
The current carrying conductors are led to the terminals on the shortest
possible way and connected. The protective conductor wire is left 8 mm
longer than would be required for the connection.
•
The conductors must be reliably connected to the terminals and no wire
must be outside the terminals.
•
The splash-proof rubber gasket and O-ring must be correctly fitted. The
fixing screws and the gland must be properly tightened again so that
splash water protection is still provided.