9. Commissioning
Changing the standard temperature
TM3400 - TM3410 thermostatic mixing valves are fitted with
a thermostatic element set to a standard temperature and are
adjusted at the factory to the standard temperature (shown in
the centre of temperature plate F, and on the packaging).
This temperature can only be changed within the limits of the
corresponding adjustment range for the mixed water.
To make a change proceed as follows:
1. Temperature plate is pierced in the centre using hexa-
gonal key included in the packaging.
2. Turning the screw clockwise raises the temperature of
mixture; accordingly to lower it, turn the key in an anti-
clockwise direction.
Standard temperature
Limits of the mixed water adjust-
set in the factory °C
40
48
55
50
10
5,0
10
5,0
1,0
0,5
1,0
0,5
0,1
0,05
0,1
0,05
0,01
0,01
10. Disposal
• Red bronze housing
• Stainless steel cut-off switch
Honeywell GmbH
GB
ment ranges °C
30-45
36-53
45-65
Tolerance of the adjustment value ±2 °K
Pre-set adjustment value
48
36
53
°C
Limits for the mixed water
adjustment range
The temperature of the hot water should be at least 5 K more
than that of the mixed water.
Adjustment of the mixed water temperature with 1 key turn
GN ½ - 1
GN 1¼ -2
aprox. 6 K
aprox. 4 K
Tolerance of the adjustment value ±1 °K
6
DN 65 and 80
aprox. 2 K
DN80
DN65
2"
1
1
/
"
2
1
1
/
"
4
1"
3
/
"
4
1
/
"
2
MU1H-1369GE23 R0511