Piping work

Freeze protection

Freeze protection solutions must use propylene glycol with a toxicity rating of Class 1 as listed in Clinical Toxicology of
Commercial Products, 5th Edition.
Ethylene glycol is toxic and must not be used in the primary water circuit in case of any cross-contamination of
the potable circuit.
WARNING
Percent Propylene Glycol [wt. %]
0
10
20
30
36
40
43
48
Setting capacity and pre-pressure of the expansion vessel
When it is required to change the default pre-pressure of
the expansion vessel(1 bar), keep in mind the following
guidelines:
Use only dry nitrogen to set the expansion vessel pre-
pressure.
Inappropriate setting of the expansion vessel
pre-pressure will lead to malfunction of the system.
Therefore, the pre-pressure should only be adjusted by a
licensed installer.
Installation height
difference(a)
<7m
No pre-pressure adjustment required.
Actions required:
>7m
(a) Installation height difference: height difference(m) between the highest point of the water circuit and the indoor unit. If
the unit is located at the highest point of the installation, the installation height is considered 0m.
When Expansion vessel has a capacity 8 liters and 1bar pre-charged.
Water volume of total system for reliable performance is minimum 50liters.
24
Freezing Points of Propylene Glycol - Water Mixtures
< 220 Litres
Pre-pressure must be increased, calculate the
appropriate value following by "Calculating
the pre-pressure of the expansion vessel".
Check if the water volume is lower than
maximum allowed water volume.
Freezing Point [ °F ]
32
26
20
10
0
-5
-10
-20
2.5
2.0
1.5
1.0
0.5
0.0
150
Water volume
Actions required:
Pre-pressure must be decreased, calculate
according to "Calculating the pre-pressure of
the expansion vessel".
Check if the water volume is lower than
maximum allowed water volume.
Expansion vessel of the unit too small for the
installation.
Freezing Point [ °C ]
0
-3
-7
-12
-18
-20
-23
-29
Operation range
200
250
300
Total water volume(ℓ)
> 220 Litres
350