Using Surge Suppressors - Allen-Bradley SLC 500 1747-L20 Instrucciones De Instalación

Controladores tipo hardware compacto
Tabla de contenido

Publicidad

All manuals and user guides at all-guides.com
Relay Contact Ratings
Maximum
Amperes
Volts
Make
240V ac
7.5A
120V ac
15A
125V dc
0.22A
24V dc
1.2A
To calculate make and break ratings for other load voltages, divide the volt-ampere
rating by the load voltage. For example:

Using Surge Suppressors

Inductive load devices such as motor starters and solenoids require the use of some
type of surge suppression to protect the controller output contacts. Switching
inductive loads without surge suppression can significantly reduce the lifetime of
relay contacts. By adding a suppression device directly across the coil of an inductive
device, you will prolong the life of the switch contacts. You will also reduce the
effects of voltage transients caused by interrupting the current to that inductive
device, and will prevent electrical noise from radiating into system wiring.
SLC 500™ Fixed Hardware Style Controllers
Amperes
Continuous
Break
0.75A
2.5A
1.5A
1.0A
2.0A
28 VA
----------------- 0.583 A
=
48V dc
Volt-amperes
Make
Break
1800 VA
180 VA
28 VA
28 VA
Publication 1747-IN008B-MU-P
19

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Slc 500 1747-l30Slc 500 1747-l40

Tabla de contenido