Electrical Characteristics; Wiring Example And How To Set The Remote Controller - Daikin FXMQ20PAVE Manual De Instalación

Ocultar thumbs Ver también para FXMQ20PAVE:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

9-2 ELECTRICAL CHARACTERISTICS

U
n
s t i
Model
Hz
Volts
FXMQ20
FXMQ25
FXMQ32
FXMQ40
FXMQ50
220-
Max. 264
50
240
Min. 198
FXMQ63
FXMQ80
FXMQ100
FXMQ125
FXMQ140
FXMQ20
FXMQ25
FXMQ32
FXMQ40
FXMQ50
Max. 242
60
220
Min. 198
FXMQ63
FXMQ80
FXMQ100
FXMQ125
FXMQ140
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A)
9-3 SPECIFICATIONS FOR FIELD SUPPLIED
FUSES AND WIRE
Power supply wiring
Model
Field fuses
Wire
FXMQ20
FXMQ25
FXMQ32
FXMQ40
H05VV-
U3G
FXMQ50
16A
FXMQ63
(NOTE 1)
FXMQ80
FXMQ100
FXMQ125
FXMQ140
Allowable length of transmission wirings and remote controller
wiring are as follows.
(1) Outdoor unit – Indoor unit:
Max. 1000 m (Total wiring length: 2000 m)
(2) Indoor unit – Remote controller:
Max. 500 m
10
o P
w
r e
u s
p p
y l
F
n a
m
Voltage
MCA
MFA
kW
range
0.6
16
0.09
0.6
16
0.09
0.6
16
0.09
1.4
16
0.140
1.6
16
0.350
1.8
16
0.350
2.3
16
0.350
2.9
16
0.350
3.4
16
0.350
3.4
16
0.350
0.6
16
0.09
0.6
16
0.09
0.6
16
0.09
1.4
16
0.140
1.6
16
0.350
1.8
16
0.350
2.3
16
0.350
2.9
16
0.350
3.4
16
0.350
3.4
16
0.350
Remote controller wiring
Transmission wiring
Size
Wire
Size
Sheathed
wire
2.5 mm
2
(2 wire)
0.75 -
1.25 mm
(NOTE 3)
(NOTE 2)
NOTE
1.
Shows only in case of protected piping. Use H07RN-F in
o
r o t
case of no protection. (Do not lighter than 60245 IEC 57.)
2.
Vinyl cord with sheath or cable (Insulated thickness : 1 mm
FLA
or more)
3.
This size is based on IEC 60335-1 (Table 11), and this
0.5
size must comply with local codes.
0.5
0.5
10. WIRING EXAMPLE AND HOW TO SET
1.1
THE REMOTE CONTROLLER
1.3
10-1 CONNECTING POWER SUPPLY, GROUND,
1.4
REMOTE CONTROLLER, AND TRANSMISSION
WIRING
1.8
(Remove the control box lid as shown below and connect each
2.3
wire.)
2.7
(1) Remove the control box lid.
2.7
0.5
0.5
0.5
1.1
1.3
1.4
1.8
2.3
2.7
2.7
(2) Lay the wires in the control box through the wire inlet on the
side of the control box.
Low-voltage wiring inlet
Transmission wiring
(Low voltage)
Remote controller wiring
(Low voltage)
2
CAUTION
• Do not lay the remote controller wiring or transmission wiring
along with the power supply wiring or other electric wiring in
the same route. Separate the remote controller wiring and
transmission wiring at least 50 mm from the power supply
wiring or other electric wiring, or otherwise malfunctions or
failures may be caused by external electric noise that may
interfere with the remote controller wiring and transmission
wiring.
• For the installation and wiring of the remote controller, refer
to the remote controller installation manual provided with the
remote controller.
• For power supply wiring, refer to the wiring diagram as well.
• Be sure to connect the remote controller wiring and
transmission wiring correctly to the right terminal block.
Screw
(3 position)
High-voltage wiring inlet
Power supply wiring
(High voltage)
Earth wiring (High voltage)
English