INSTALLATION INSTRUCTIONS

C-WP-A-TWP Series
MOUNTING USING CONDUIT
1.
Remove lens assembly by loosening screws on side of frame.
Swing lens assembly open, disconnect quick-connect wiring
connector, and slide lens assembly on hinges to remove from
mounting box. See Figure 1.
2.
Remove appropriate conduit plug from back wall or side of
mounting box.
3.
Drill holes at knockout locations in the four corners of the mounting
box for attachment of fixture to mounting surface. See Figure 4.
4.
Attach conduit to mounting box at chosen threaded opening.
NOTE: To ensure a watertight seal, teflon tape should be used on
conduit threads.
5.
Attach the mounting box to the mounting surface using customer
supplied fasteners appropriate for the mounting surface. Fasteners
should be passed through the knockout holes removed in Step 3
and threaded into mounting surface.
NOTE: A high grade caulking material, such as silicone rubber,
should be used between the four gaskets in the corners and the
mounting surface to prevent water entry into the fixture or junction
box.
6.
Use switch inside moutning box to set desired color temperature.
See Figure 5.
NOTE: Power must always be OFF when adjusting color
temperature.
7.
Rotate knob to select desired wattage for fixture. See Figure 6.
NOTE: Power must always be OFF when adjusting wattage.
8.
Make wiring connections per the Electrical Connections section.
9.
Replace the lens assembly on hinges, re-connect quick-connect
wiring connectors, and swing lens into place. Retighten screws
that were loosened in Step 1 above.

ELECTRICAL CONNECTIONS

Fixture is equipped with universal volt driver 120-277V
(ie. 120V, 208V, 240V or 277V)
PHASE TO NEUTRAL WIRING 120/277V
1. Connect supply ground to driver ground (green) lead
and ground (green) lead attached to housing.
2. Connect supply common to fixture neutral (white) lead.
3. Connect supply Vin to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
PHASE TO PHASE WIRING 208/240V
1. Connect supply ground to driver ground (green) lead
and ground (green) lead attached to housing.
2. Connect supply L1 (Hot) to fixture neutral (white) lead.
3. Connect supply L2 (Hot) to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no
wires are pinched.
http://lighting.cree.com/warranty
Document:
LPN00703X0001A0_A
Created By:
TMT
FIGURE 4
FIGURE 5
FIGURE 6
FCC NOTICE Class A
CAUTION: Changes or modifications not expressly approved could
void your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
CAN ICES-005 (A)/NMB-005 (A)
|
866.924.3645