English
6. Connect CS141 with your network
Connect the LAN port of your CS141 with the according network
node.
7. Login and check settings
1. Enter the IP address of your CS141 and log in with current pass-
words.
2. The upper area should show „OK".
At the UPS monitor, UPS operational state data will be displayed.
3. The quick configuration is finished, the CS141 will monitor and log
your UPS.
8. Using the DHCP mode
For the DHCP mode, an internal DHCP server is mandatory. In
this operating mode, the CS141 will query for a valid IP address.
A local IP address configuration is not necessary, but we recom-
mend to use the manual option:
If the DHCP server is not reachable, the CS141 will boot and start
with a manually configured IP address.
Furthermore, some options like RCCMD requires a static IP
address. The DHCP server may change it dynamically.
How to activate the DHCP mode:
1. Put the sliding switch to the rightt position.
2. Connect the power supply or insert the slot card into the accord-
ing slot of the UPS.
3. Connect the CS141 with your local network.
The CS141 will start and boot with the IP address provided by the
local DHCP server. Access the CS141 with the according IP
address directly.
Note:
Do not forget to configure the UPS model and for more informati-
on as well as the complete CS141 user's guide, visit us on
www.generex.de
Protect your network: Use the RCCMD software client
Use build-in functions of the CS141 directly and optimize your entire network protection
in case of a power failure: Find a copy of the user-friendly and powerful RCCMD client
on your support CD or visit us to download the latest version at www.generex.de.
Each copy of RCCMD comes with an evaluation key and detailed installation instruc-
tions for the immediate start of emergency network managing solutions.
Setting up an RCCMD emergency job at the CS141 in just 5 steps
1. At UPS events, search for
2. At the configuration dialog, select as job
3. At parameters, enter the
4. If required, customize the job timing about the job to be triggered, eg "At 240 seconds remaining time" ...
5. Press „Save" to save the job to this event.
For security reasons, we recommend to add the same job at the event "Battery low", but this time without any time
delay: This avoids premature shutdown of the UPS due to low battery level before your server was shut down ac-
cordingly.
„Power
Fail" and press „+" to start the job configuration dialog.
„RCCMD
„IP
address" of the RCCMD client (As a standard, RCCMD uses port 6003).
Shutdown".
Sliding switch to right
EU: 230V AC / 12V DC
US: 120V AC / 12V DC
http://www.generex.de
- Download
- Software
- RCCMD Download