INSTRUCTION MANUAL
Digital Manifold for HVAC/R Systems
MANUAL DE INSTRUCCIONES
Manifold Digital HVAC/R
SPECIAL FEATURES
• Low battery indicator
• Displays 63 refrigerants
• Displays corresponding saturation, dew or bubble point temperature for current pressure
• Displays sensor/thermocouple temperature, superheat/subcool
temperature and deep vacuum when connected
• Includes back-lit display for easy reading in darker areas
• 9V DC battery with optional AC/DC adapter
• Free floating piston seal seat aluminum block with sight glass
• Auto-Off with disabling capability
SPECIFICATIONS
• Pressure Display: PSI, INHg, Bar, MPa, Kg/cm
• Temperature Display: °F or °C
• Deep Vacuum Display: Micron, mBar, KPa, mmHg, Pa, Torr, mTorr
• Sensing Resolution: 1 psi (.07 Bar, .007 MPa, .07 Kg/cm
• Sensing Accuracy: ±1 psi or 1% of reading (whichever is greater)
• Working Pressure: 0 to 750 psi (52 Bar, 5 MPa, 52 Kg/cm
• Proof Pressure: 1000 psi (70 Bar, 7 MPa, 70 Kg/cm
(Tolerable pressure without internal damage)
• Refrigerant Temperature Range: -40 to 200°F (-40 to 93°C)
• Operating Temperature: 32 to 122°F (0 to 45°C)
• Temperature Accuracy: ±1˚F (±0.5˚C) between 32 to 160˚F (0 to 71˚C)
• Storage Temperature: 32 to 120˚F (0 to 49˚C)
• Connections: 1/4" M-Flare
• Power: 9V DC battery with optional AC/DC adapter
• Battery Life: 30-36 hours pressure and temperature mode only (continuous use)
25-30 hours vacuum and backlight mode (continuous use)
• Auto-Off: 15 min. with disabling capability
WARNING!!
• Wear Safety Glasses / Wear Gloves
• Keep the manifold in a dry place. Do not allow moisture to enter the unit.
• Do not vent refrigerant into the atmosphere.
• If eyes come in contact with refrigerant, immediately flush with plenty of water.
Seek medical attention immediately.
• STATIC DISCHARGE: Climates in some parts of the world are conducive to creating
static electric build up (ESD). Your digital manifold has been designed to eliminate
the damaging effects of ESD. In some extreme cases, ESD will be apparent on your
digital manifold by a lack of response or an inability to turn off the unit. In the rare
case that this occurs, simply disconnect the battery, wait 1 minute and reconnect
the battery. The digital manifold will "reboot" itself and operate normally once the
2
2
www.mastercool.com
MANIFOLD WITH OPTIONAL
ACCESSORIES SHOWN
2
)
2
) (does not display 0-5 psi)
)
English
1

Publicidad

Tabla de contenido
loading

Resumen de contenidos para MasterCool Digital Manifold

  • Página 1 ESD. In some extreme cases, ESD will be apparent on your digital manifold by a lack of response or an inability to turn off the unit. In the rare case that this occurs, simply disconnect the battery, wait 1 minute and reconnect the battery.
  • Página 2 • The display will show zero (0) whenever the measurement falls below the following readings: 3 PSI, 0.2 Kg/cm, 0.2 BAR, 0.02 mPA or 6 in-Hg • The digital manifold is normally shipped with vacuum and temperature sensors that are calibrated with the companion manifold. In the event the other sensors are provided by another source, please contact Mastercool Inc.
  • Página 3 • Connect the vacuum cable to the manifold. Connect the other end of the vacuum gauge to the system. (An additional TEE fitting (Mastercool #99333) or an isolation valve may be required.) Press the VACUUM button and select the desired unit.
  • Página 4 Measuring superheat is your best indication on a fixed orifice system of the proper refrigerant charge and operating conditions. If everything else is working properly and the actual superheat is too high, add refrigerant. If it’s too low, remove refrigerant. www.mastercool.com...
  • Página 5 (outdoor air temperature), indoor wet bulb, and the manufacturers target superheat chart or subcooling chart. You can use Mastercool part number 52232 Humidity Temperature Meter for both indoor wet bulb and outdoor dry bulb. GENERIC TARGET SUPERHEAT & SUBCOOLING CHARTS* *The required superheat chart is an example of a generic superheat chart of a typical fixed...
  • Página 6: Optional Accessories

    Warranty becomes valid to the original user, effective on the purchase date. A copy of an invoice along with a registration card must be sent to 1 Aspen Drive, Randolph, NJ 07869 to validate the warranty. For further service please contact (973) 252-9119. www.mastercool.com...
  • Página 7: Caracteristicas Especiales

    • El manómetro (manifold / árbol de carga) digital se despacha normalmente con el censor de vacío y temperatura calibrados al manómetro que acompañan. En caso que se use un censor de otro suplidor, contáctese con Mastercool para darle las instrucciones de calibración correcta.
  • Página 8 Presione el botón ENTER para confirmar. • La exhibición de vacío se apagará despues de 15 minutos automáticamente. Presione el botón ON/OFF y el botón VACUUM para encender la unidad. Permita de 30 a 45 segundos para que el sensor se caliente y www.mastercool.com...
  • Página 9: Diagnosticando La Presion Y La Temperatura En El Sistema

    • Conecte el cable de vacío al analizador. Conecte el otro extremo del indicador de vacío al sistema. (un accesorio adicional en forma de T (Mastercool #99333) ó una valvula de aislamiento podrian ser requeridos.) Presione el botón de VACUUM y seleccione la unidad deseada.
  • Página 10: Calibracion De La Abrazadera Termopar

    Para estar seguros de que el liquido no entra en el compresor en el peor de los casos, los fabricantes de AC han publicado tablas. las tablas indican, que el sobrecalentamiento deve de estar dando una medida de humedad en el interior y en www.mastercool.com...
  • Página 11: Objetivo Sobrecalentamiento Y Subenfriamiento

    Usted puede utilizar el medidor de temperatura y humedad Mastercool parte numero 52232 para los dos, humedad en el interior y temperatura al aire libre.
  • Página 12: Lista De Partes Y Accesorios

    La garantia es válida para el usuario original y se hace efectiva a partir de el dia de su compra. La copia de una factura junto con una tarjeta de registración deverán de ser enviadas a 1 Aspen Drive, Randolph, NJ 07869 para validar la garantia. Para servicio Adicional, por favor contactenos al tel: (973) 252-9119. www.mastercool.com 99103-ES-INST...