INSTRUCTION MANUAL
Digital Manifold for HVAC/R Systems
MANUAL DE INSTRUCCIONES
Manifold Digital HVAC/R
SPECIAL FEATURES
• Low battery indicator
• Displays 63 refrigerants
• Displays corresponding saturation, dew or bubble point temperature for current pressure
• Displays sensor/thermocouple temperature, superheat/subcool
temperature and deep vacuum when connected
• Includes back-lit display for easy reading in darker areas
• 9V DC battery with optional AC/DC adapter
• Free floating piston seal seat aluminum block with sight glass
• Auto-Off with disabling capability
SPECIFICATIONS
• Pressure Display: PSI, INHg, Bar, MPa, Kg/cm
• Temperature Display: °F or °C
• Deep Vacuum Display: Micron, mBar, KPa, mmHg, Pa, Torr, mTorr
• Sensing Resolution: 1 psi (.07 Bar, .007 MPa, .07 Kg/cm
• Sensing Accuracy: ±1 psi or 1% of reading (whichever is greater)
• Working Pressure: 0 to 750 psi (52 Bar, 5 MPa, 52 Kg/cm
• Proof Pressure: 1000 psi (70 Bar, 7 MPa, 70 Kg/cm
(Tolerable pressure without internal damage)
• Refrigerant Temperature Range: -40 to 200°F (-40 to 93°C)
• Operating Temperature: 32 to 122°F (0 to 45°C)
• Temperature Accuracy: ±1˚F (±0.5˚C) between 32 to 160˚F (0 to 71˚C)
• Storage Temperature: 32 to 120˚F (0 to 49˚C)
• Connections: 1/4" M-Flare
• Power: 9V DC battery with optional AC/DC adapter
• Battery Life: 30-36 hours pressure and temperature mode only (continuous use)
25-30 hours vacuum and backlight mode (continuous use)
• Auto-Off: 15 min. with disabling capability
WARNING!!
• Wear Safety Glasses / Wear Gloves
• Keep the manifold in a dry place. Do not allow moisture to enter the unit.
• Do not vent refrigerant into the atmosphere.
• If eyes come in contact with refrigerant, immediately flush with plenty of water.
Seek medical attention immediately.
• STATIC DISCHARGE: Climates in some parts of the world are conducive to creating
static electric build up (ESD). Your digital manifold has been designed to eliminate
the damaging effects of ESD. In some extreme cases, ESD will be apparent on your
digital manifold by a lack of response or an inability to turn off the unit. In the rare
case that this occurs, simply disconnect the battery, wait 1 minute and reconnect
the battery. The digital manifold will "reboot" itself and operate normally once the
2
2
www.mastercool.com
MANIFOLD WITH OPTIONAL
ACCESSORIES SHOWN
2
)
2
) (does not display 0-5 psi)
)