Test Run; Before Test Run - Mitsubishi Electric PKA-A24KA7 Manual De Instalación

Ocultar thumbs Ver también para PKA-A24KA7:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6. Electrical work
Function table
Select unit number 00
Mode
Power failure automatic recovery
Indoor temperature detecting
LOSSNAY connectivity
Power voltage
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Filter sign
Fan speed
*1 When the power supply returns, the air conditioner will start 3 minutes or 1 minute later (hinge on outdoor unit).

7. Test run

7.1. Before test run

After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power
supply or control wiring, wrong polarity, and no disconnection of one
phase in the supply.
Use a 500-volt megohmmeter to check that the resistance between the
power supply terminals and ground is at least 1.0 MΩ.
7.2. Test run
Refer to the installation manual that comes with each remote controller for details.
7.3. Self-check
Refer to the installation manual that comes with each remote controller for details.
RF thermostat is not established.
• Refer to the following tables for details on the check codes. (IR wireless remote controller)
[Output pattern A]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp flash
Off
pattern
Approx. 2.5 sec.
Self-check
starts
(Start signal
Number of flashes/beeps in pattern indicates the check
received)
code in the following table (i.e., n=5 for "P5")
[Output pattern B]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp flash
Off
pattern
Approx. 2.5 sec.
Self-check
starts
(Start signal
received)
12
Settings
Not available
Available
Indoor unit operating average
Set by indoor unit's remote controller
Wired remote controller's internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
230 V
208 V
Settings
100Hr
2500Hr
No filter sign indicator
Silent
Standard
High ceiling
Beep
Beep
Beep
Beep
1
2
3
n
st
nd
rd
th
On
On
On
On
0.5 sec.
0.5 sec.
0.5 sec.
0.5 sec.
Beep
Beep
1
st
2
nd
On
On
On
Approx. 3 sec.
0.5 sec.
0.5 sec.
Number of flashes/beeps in pattern indicates the check
code in the following table (i.e., n=5 for "U2")
Mode No.
Wired remote controller
*1
Mode No.
Wired remote controller
Do not carry out this test on the control wiring (low voltage circuit)
terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 MΩ.
Insulation resistance.
Beep
Beep
1
2
· · · Repeated
st
nd
Off
On
On
Approx. 2.5 sec.
0.5 sec.
0.5 sec.
Number of flashes/beeps in pattern indicates
the check code in the following table
Beep
Beep
3
rd
n
th
On
On
Off
0.5 sec.
0.5 sec.
Approx. 2.5 sec.
Setting
Initial
no.
setting
1
01
2
1
02
2
3
1
03
2
3
1
04
2
Setting
Initial
no.
setting
1
07
2
3
1
08
2
3
Beep
Beep
1
st
2
nd
· · · Repeated
On
On
On
Approx. 3 sec.
0.5 sec.
0.5 sec.
Number of flashes/beeps in pattern indicates
the check code in the following table
setting
setting

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Pka-a30ka7Pka-a36ka7

Tabla de contenido