Important Safety Information
CAUTION
It is highly recommended that you do not open or close
the stop valves when the outdoor temperature is below
-5°F (-21°C) as this may cause refrigerant leakage.
Make sure power is turned on for at least 12 hours
after periods of being powered down in an 32 °F (0° C)
environment or lower.
Do not touch the fins of the coil. Touching the coil fins
could result in damage to the fins or personal injury such
as skin rupture.
Ensure the power circuit capacity is adequate for all loads
connected to the electrical service panel. Increase the
conductor and panel capacity if the total electrical loads
exceed the power source capacity.
Contact the power utility if the power provided is below
equipment rating plate requirements.
Be sure to install a breaker of the specified capacity.
Regulation of cables and breaker differs from each
locality, refer in accordance with local rules.
Do not use existing refrigerant lines.
READ AND SAVE THESE INSTRUCTIONS
For more help, visit GEAppliances.com/ductless or call the consumer help line at 844-487-9443.
CAUTION
• Aluminum electrical wiring may present special
problems - consult a qualified electrician.
• When the unit is in the STOP position, there is still
voltage to the electrical controls.
31-5000560 Rev. 3
Use refrigerant tubing that is clean and free of any
contamination which may cause damage to the system
including sulfur, copper oxide, dust, metal chips, powder,
oil or water.
Avoid brazing lines together. Use a continuous length of
copper tubing as oxides formed during improper brazing
techniques can damage the equipment.
Do not use copper pipes that have a collapsed, deformed,
or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may
become blocked with contaminants.
Improper line sizing will degrade performance. Peak
pressure of R410A is much higher than R22. Use copper
tubing with adequate wall thickness.
To prevent breaking of the pipe, avoid sharp bends. Bend
the pipe with a radius of curvature of 4 in. (100 mm ) or
more.
If the pipe is bent repeatedly at the same place, it will
break.
BEFORE YOU BEGIN
Read these instructions carefully and completely.
IMPORTANT
■
local inspector's use.
IMPORTANT
■
codes and ordinances.
■ Note to installer – Be sure to leave these
instructions with the Consumer.
■ Note to consumer – Keep these instructions for
future reference.
■ Skill level – A licensed certified technician (to
handle refrigerant R-410A, recovery, etc) and a
qualified electrician are required for installation and
service of this split heat pump system.
■ Proper installation is the responsibility of the
installer.
■ Product failure due to improper installation is not
covered under the limited warranty.
■ For personal safety, this system must be properly
grounded.
■ Protective devices (fuses or circuit breakers)
acceptable for installation are specified on the
nameplate of each unit.
■ Make sure to avoid wiring or plumbing inside the
wall when installing.
– Save these instructions for
– Observe all governing
5