0x10...0x1F
Coil status
0x20...0x2F
Coil status
B3
Cooling mode
B4
Auto mode
B5
Reserve
B6
Reserve
B7
ON/OFF
B8
High fan speed
B9
Middle fan speed
B10
Low fan speed
B11
Breeze fan speed
B12
Reserve
B13
Reserve
B14
Reserve
B15
Auto fan speed
1
B0
ECO
B1
Heater
B2
Swing
B3
Reserve
B4
Reserve
B5
Reserve
B6
Reserve
B7
DRY
B8
Horizontal swing
B9
Reserve
B10
Water pump
B11
Reserve
B12
B13
Mode lock
B14
Mode lock switch
B15
Remote lock
2
B0
E0 phase error
B1
E1
Communication
error
B2
E2 T1 sensor error
B3
E3
T2A
error
B4
E4
T2B
error
B5
E5 Outdoor
temp. sensor
error
31
1: Valid, 0: Invalid
1: Valid, 0: Invalid
Reserve, 0
Reserve, 0
1=ON,0=OFF
1: Valid, 0: Invalid
1: Valid, 0: Invalid
1: Valid, 0: Invalid
1: Valid, 0: Invalid
Reserve, 0
Reserve, 0
Reserve, 0
1: Valid, 0: Invalid
1: ON; 0: OFF
1: ON; 0: OFF
1: Valid, 0: Invalid
Reserve, 0
Reserve, 0
Reserve, 0
Reserve, 0
1: ON; 0: OFF
1: ON; 0: OFF
Reserve, 0
1: ON; 0: OFF
Reserve, 0
00: Lock in OFF mode or
Unlock
01: Lock in cooling, 10: Lock in
heating, 11 Lock in fan mode
1: Valid, 0: Invalid
1: Valid, 0: Invalid
1: Error, 0: Normal
1: Error, 0: Normal
1: Error, 0: Normal
sensor
1: Error, 0: Normal
sensor
1: Error, 0: Normal
1: Error, 0: Normal