Quick Start Guide
English
CP 210-R
Differential pressure, air velocity, air flow and
temperature transmitter
Range from ±100 to
±10 000 Pa
to model)
2 relay outputs
General features
Power supply
Output
Common mode voltage <30 VAC. Maximum load: 500 Ohms (0/4-20 mA). Minimum load: 1 K Ohms (0-5/10 V)
Relay outputs
Galvanic isolation
Consumption
Electrical connection
Screw terminal block for cables 2.5 mm
PC communication
Environment
Autozero
Manual by push-button; Automatic by solenoid valve (only models CP211 and CP212)
Type of fluid
Conditions of use (°C/%RH/m)
Storage temperature
Security
European directives
Features of the housing
Matierial
ABS V0 according to UL94
Protection
IP65
75 x 40 mm, LCD 19 digits 2 lines
Display
Height of digits:
Values: 10 mm; Units: 5 mm
Connection
Ribbed Ø6.2 mm (CP211/212/213)
Pass-through
For cables Ø6 mm maximum
Cable gland
For cables Ø8 mm maximum
Weight
340 g
Two 4-wire analogue outputs
(according
0-5 / 10 V
0-5/10 V or 0/4-20 mA
4-20 mA
Air velocity and air
flow calculation
with or without display
24 Vac / Vdc ±10%. 100-240 Vac, 50-60 Hz
Warning: risk of electric shock
2 x 4-20 mA or 2 x 0-20 mA or 2 x 0-5 V or 2 x 0-10 V (4 wires)
2 changeover relays. NO: 5A / NC: 3A / 240 Vac
Inputs and outputs (100-240 Vac models). Device fully protected by
DOUBLE ISOLATION or REINFORCED ISOLATION
Outputs (24 Vac/Vdc models)
CP210-B: 6 VA / CP210-H: 8 VA
2
. Carried out according to the code of good practice
USB-Mini Din cable
Air and neutral gases
Air and neutral gases
From -10 to +50°C. In non-condensing condition. From 0 to 2000 m.
From -10 to +70°C
Protection class II; Pollution degree 2; Overvoltage category 2 (OVCII)
2014/30/EU EMC; 2014/35/EU Low Voltage; 2011/65/EU RoHS II; 2012/19/EU WEEE
All dimensions are in mm
125
59
Symbols used
For your safety and in order to avoid any damage of the device, please follow the procedure described in
this document and read carefully the notes preceded by the following symbol:
The following symbol will also be used in this document, please read carefully the information notes
indicated after this symbol:
Connections
2
(optional)
Power supply type (b) specified on the label
on the side of the transmitter
Pt100
terminal
block
1 2 2'
Electrical connections as per NFC15-100 standard
For transmitters with 24 Vdc power supply:
For transmitters with 24 Vac power supply:
24 Vac power supply
class II EN61558-2-6 standard
230 Vac
230 Vac
For transmitters with 100-240 Vac power supply:
9
1
8
7
3
10
5
4
6
11
CP21X-HXX-R
CP21X-BXX-R
Power supply: 100-240 Vac
Power supply: 24 Vac/Vdc ±10 %
50-60 Hz 8 VA
50-60 Hz 6 VA
Output: 0/4...20 mA / 0...5/10 V
Output: 0/4...20 mA / 0...5/10 V
100-240 Vac
24 Vac/Vdc
(a)
(c)
(c)
ou
Analogue output 1
Analogue output 2
For 24 Vdc power
For 24 Vac power
(out 1)
(out 2)
supply models
supply models
-
Neutral (N)~
+
Phase (L)~
NO: normaly opened
COM: common
NC: normaly closed
*Fuse present only for 100-240 Vac models.
Every fuse replacement must be performed witht a power off device using a TR5 630 mA 250 V fuse.
This connection must be made by a formed and qualified technician. To make the connection, the transmitter must not
be energized. Before making the connection, you must first check the power supply indicated on the transmitter board
(see (b) on "Connections" part). The presence of a switch and a circuit breaker upstream the device is compulsory.
The selection of the output signal in voltage (0-10 V or 0-5 V) or in current
(4-20 mA or 0-20 mA) is made via the DIP switch (d) of the electronic board
-
N-
of the transmitter: put the on-of switches as shown in the table below:
24 Vdc
Power supply
L+
+
Configurations
Combinations
N
N-
Pe
N
L
L+
L
Connection of the output in current
or
4-20 mA:
Pe
0-5/10 V
N
-
N-
N
L
L+
L
Power supply
Regulator display or
N
PLC/BMS passive type
N-
100-240 Vac
Power supply
L+
L
4-20 mA output
On 100-240 Vac models, if a fuse protection is used for the power line, it is imperative to use delayed-action
fuses in order to absorb the surge of current when first turned on the transmitter.
1. DIP switch (d)
2. Pt100 terminal block
3. Solenoid valve (only on CP211/212)
4. LCC-S software connection
5. Autozero
6. Pressure connections
7. Relays
8. Analogue outputs (a)
9. F3.20* fuse
10. Power supply terminal block (c)
11. Cable glands
(c)
ou
For 100-240 Vac
power supply models
Operational grounding
Neutral (N)~
Phase (L)~
Relays 1 and 2
4-20 mA
0-10 V
0-5 V
0-20 mA
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
Connection of output in voltage
0-10 V:
0/4-20 mA
0-5/10 V
0/4-20 mA
-
+
+
A
V
Regulator display or
PLC/BMS passive type
0-10 V output