One Touch™ Test Mode
To speed up installation and testing, One-Touch™ testing is provided which allows the controller functionality to be tested at the controller
or reader.
Test
Action
Normal Operation
Hold down One-Touch™ button for less than 2
seconds. Present keys, press RTE switches and
One-Touch™ View
observe LEDs.
Mode
Automatically exits after 2 minutes.
One-Touch™ Active
Hold down One-Touch™ button for 2 to 4
Mode
seconds.
Present a key to each reader (the lock will
activate).
Reader and Request
Press the Request to Exit switch (the lock will
to Exit Test
activate).
Open the door contact.
Present a key to a reader, press the Request to Exit switch and
open the door contact simultaneously.
Auxiliary and Lock
Remove link to 0V on tamper or open circuit tamper switch.
Relays Test
Remove link to 0V on emergency override or leave open circuit
tamper switch.
Remove the link between TAMP and 0V on the Tamper &
Override terminal block.
Tamper and Override
Test
Remove the link between OVRD and 0V on the Tamper &
Override terminal block.
Hold down One-Touch™ button for less than 2
Leave One-Touch™
seconds. One-Touch™ Test mode will
Active Test mode
automatically be timed out after 1 hour,
power up or power down.
Observation
Controller
System status: GREEN
flashes at normal rate.
Green
Door status: All LEDs
off.
Green-Red-Yellow
System status GREEN
flashes at normal rate.
Green
Door status: GREEN
on, valid key
presented to reader.
Green-Red-Yellow
Door status: GREEN
flashes, invalid key
presented to reader.
Green-Red-Yellow
Door status: RED on,
door open.
Green-Red-Yellow
Door status: YELLOW
on, RTE switch has
been pressed.
Green-Red-Yellow
System status: GREEN
flashes faster than
normal.
Green
Door status: GREEN
flashes once for SIGA,
twice for SIGB.
Green-Red-Yellow
Door status: GREEN
flashes three times
and YELLOW is on.
Green-Red-Yellow
Door status: GREEN
flashes four times and
RED is on.
Green-Red-Yellow
The appropriate auxiliary relay is activated.
Both auxiliary relays are activated.
The auxiliary relay is activated.
The auxiliary relay is activated but the door relays are unaffected.
Both auxiliary and lock relays are activated, the door opens and the lock
operates.
System status: GREEN
flashes at normal rate
again.
Green
- 5 -
Reader
Normal operation of the reader.
Red
Normal operation of the reader
LED changes, e.g. if default is red it
changes to green.
Green
Reader LED flashes once for SIGA,
twice for SIGB.
Red
Reader LED flashes three times.
Red
Reader LED flashes four times.
Red
Reader LED returns to normal
operation.
Red