9
Indication Decription
Condition
Sounder Indication
Normal
Off
0.5 s on, 0.5 s off for 3 cycles, then 1.5 s
off (repeating until manual hush or smoke dissipated)
Alarm
For other interconnected smoke alarms:
0.5 s on, 0.5 s off for 3 cycles, then 1.5 s
off (repeat 3 times)
0.5 s on, 0.5 s off for 3 cycles, then 1.5 s
off (repeating)
Test
For other interconnected smoke alarms:
0.5 s on, 0.5 s off for 3 cycles, then 1.5 s
off (repeating)
Hush
Off
Smoke chamber
1 audible beep every 40 s (separately to
fault
the LED)
For the smoke alarm with the depleted
battery: 1 audible beep every 40 s
(synchronously with the LED)
Low battery
For other interconnected smoke alarms:
2 audible beeps every 4 h
(synchronously with LED)
Coding in progress
Off
Coding successful
1 short beep
Any time before the next alarm, press
the Test button, 3 audible beeps every 1 s
Local alarm
memory
Release of the Test button shall reset the
alarm
End-of-life
3 audible beeps every 40 s
Factory default
1 audible beep
settings
Red LED
1 flash every 320 s
2 flashes every 1 s
For other interconnected
smoke alarms: Off
2 flashes every 1 s
For other interconnected
smoke alarms: Off
2 flashes every 1 s
1 flash every 40 s (separately
to the sounder)
For the smoke alarm with the
depleted battery: 1 flash every
40 s(synchronously with the
sounder)
For other interconnected
smoke alarms: 2 flashes every
4 h (synchronously with
sounder)
1 flash every 1 s up to 60 s
Off
2 flashes every1 s
Green LED
On for 10 s
3 flashes every 40 s
up to 24 h