Connecting
WARNING
Hazardous voltages from the mains power input or heat
emitter lines
May cause death, serious injury or damage to property
Dangerous voltages may be present on incoming lines
from the supply and to heat emitters.
Before work starts on connecting the HCS3200 heating
controller, the incoming supply and heat emitter lines must
be disconnected and secured against being switched on
again.
NOTICE
The connected loads (heat emitter and fans) must not
exceed the permissible total power of the device, namely
25,200 W.
Connection element locations: See Figure 4
Connection diagram: See Figure 7
Recommended connector accessories with order number:
See Figure 6
You can procure further accessories for X1 and X2 via the
Harting (http://www.harting.com/en/home/).
You can procure accessories for X3 and X4 via Siemens
Industry Mall (www.siemens.com/siplus/mall).
X1 Mains connection / protective conductor connection
X2 Connection of emitter / fan
X3 PROFIBUS DP / 24 V DC supply voltage
X4 PROFIBUS DP / 24 V DC supply voltage
WARNING
Electric shock hazard / fire hazard
Danger to life or danger of serious injury
● Voltages to ground of 230 V AC may be present at X2.
The connection cables must have double or reinforced
insulation.
● The protective conductor for the device is connected to
plug connector X1.
The protective conductor must be attached to the
connector in accordance with the manufacturer's
instructions.
NOTICE
The phase sequence Lx to Ly must be clockwise.
Otherwise, the fault diagnostics of the external fan will not
work properly.
4
Technical specifications
Connection data
Rated voltage
Switching capacity per phase
Number of output channels
Maximum switching capacity
per output channel
Fuse for each output channel
Total switching capacity of
the device
Overvoltage category
Fan output
Number of fan outputs
Power
Fuse
Controller power supply
Voltage
Current consumption
Environmental conditions
Note: For indoor use only.
Ambient temperature in
operation
Ambient temperature during
storage and transport
Relative air humidity during
operation and storage
Degree of protection
Degree of pollution
Maximum height above sea
level
Mechanical specifications
Weight
Dimensions (W x H x D)
Approvals / standards
CE
Electrical safety
Technical Assistance
Telephone: +49 (0) 911-895-5900 (8°° - 17°° CET)
Email: technical-assistance@siemens.com
Internet: www.siemens.com/automation/support-request
Additional documentation
You will find further information (e.g. on parameterization,
service, etc.) in Siemens Industry Online Support
(http://support.automation.siemens.com/WW/view/en/10807
371/133300).
400 V AC (±10 %),
230 V AC (±10%) to N,
50/60 Hz
63 A
9
4 kW at 400 V AC
16 V (internally
accessible)
25200 W
Category III
1
60 ... 500 W at 230 V
4 A (internally accessible)
24 V DC (±20 %),
external, PELV
Typical: 170 mA
Max.: 250 mA
0 °C to 50 °C
-40 °C to +70°C
95 % at 25 °C, decreasing
linearly to 50 % at 50 °C
IP65
2
2000 m
Approx. 15 kg
300 mm x 380 mm x 200
mm
Directive 2006/95/EC
EMC 2004/108/EC
DIN EN 61010-1
SIPLUS HCS3200
A5E31618897A/002, 03/2013