Descargar Imprimir esta página

Sullair SRC Serie Manual De Uso página 4

Publicidad

English
3.3
Versions
Air--- cooled version (Ac)
Y
Do not create cooling air recirculation situations. Do not
obstruct the ventilation grilles.
3.4
Tips
Y
To prevent damage to the internal parts of the dryer and air
compressor, avoid installations where the surrounding air con-
tains solid and/or gaseous pollutants (e.g. sulphur, ammonia,
chlorine and installations in marine environments).
3.5
Electrical connection
Use approved cable in conformity with the local laws and regula-
tions (for minimum cable section see par. 8.3).
Connected to terminals "L and N " for single--- phase machines
and to terminals "L1--- L2--- L3" for three--- phase machines.
Install a differential thermal magnetic circuit breaker with con-
tact opening distance of 0.12 inches (3 mm) ahead of the system
(IDn = 0.3A) (see the relevant current local regulations).
3.6
Condensate drain connection
Y
Make the connection to the draining system, avoiding con-
nection in a closed circuit shared by other pressurized discharge
lines. Check the correct flow of condensate discharges. Dispose
of all the condensate in conformity with current local environ-
mental regulations.
4
Commissioning
4.1
Preliminary checks
Before commissioning the dryer, make sure:
a) installation was carried out according to that given in the sec-
tion 3;
b) the air inlet valves are closed and that there is no air flow
through the dryer;
c) the power supply is correct;
4.2
Commissioning
Start the dryer before the air compressor;
For models SRC- -150 --- SRC- -200 (see par. 5.1):
S switch the power on by turning the Main disconnector switch
&
to "I ON" so that the green line lamp illuminates.
For models SRC- -250 --- SRC- -1000 (see par. 5.2):
S switch the power on by turning the MAIN SWITCH
"I ON": the POWER LED (2) lights up turning yellow;
x
S press
: the POWER LED (2) turns green and the com-
pressor switches on; the dew point is displayed.
Y
Scroll Compressor: if connected with the wrong phase se-
quence it turns in the opposite direction, with the risk of being
damaged (in this case it is very noisy); immediately invert the
phases.
Y
Fans (Ac version): if connected with the wrong phase se-
quence they turn in the opposite direction, with the risk of being
damaged (in this case the air flows from the condenser grilles
instead of the fan grille --- see par. 8.6 for correct air flow); imme-
diately invert two phases.
a) Wait 10 minutes, then slowly open the air inlet valve;
b) slowly open the air outlet valve: the dryer is now drying.
4.3
Operation
a) Leave the dryer on during the entire period the air compres-
sor is working;
b) the dryer operates in automatic mode, therefore field settings
are not required;
c) in the event of unforeseen excess air flows, by--- pass to avoid
overloading the dryer;
d) avoid air inlet temperature fluctuations.
4.4
Stop
a) Stop the dryer 2 minutes after the air compressor stops or in
any case after interruption of the air flow;
b) make sure compressed air does not enter the dryer when the
dryer is disconnected or if an alarm occurs.
For models SRC- -150 --- SRC- -200 (see par. 5.1):
&
S Turn the Main disconnector switch
the power off.
For models SRC- -250 --- SRC- -1000 (see par. 5.2):
x
S Press
S Turn the MAIN SWITCH
&
er off.
to
5
Control
5.1
Control panel (SRC- - 150 --- SRC- - 200)
QS
Main disconnector switch (dryer ON---OFF)
HL
On lamp (green, signals that dryer is operating)
HLA
Alarm lamp (red, signals that dryer is in alarm)
Dew point thermometer:
green = dewpoint ideal
T0
red
blue = dewpoint too low
to "O OFF" to switch
SRC- - 150 --- SRC- - 1000
: the POWER LED (2) turns yellow again;
&
to "O OFF" to switch the pow-
QS
HL
HLA
T0
= dewpoint too high
2

Publicidad

loading