Descargar Imprimir esta página

Honeywell NOTIFIER NRX-REP Instrucciones De Instalación página 2

Ocultar thumbs Ver también para NOTIFIER NRX-REP:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Figure 4: Battery Installation and Rotary Address Switches
1
+
3
+
ROTARY ADDRESS SWITCHES
4a
4b
4c
4d
N200-304-00
NOTE POLARITY
2
+
+
4
+
4 x Duracell
Ultra 123
Repeater Status LEDs
Repeater Status
Power-on initialisation
(no fault)
Fault
Un-commissioned
Sync
Normal
Idle (low power mode)
Notifier by Honeywell, Brooks Road, Lewes, East Sussex, BN7 2BY, UK
PROGRAMMING
To load network parameters into the RF repeater, it is necessary
to link the RF gateway and the RF repeater in a configuration
operation. At commissioning time, with the RF network devices
powered on, the RF gateway will connect and programme them
with network information as necessary. The radio repeater then
synchronises with its other associated devices as the RF mesh
network is created by the gateway. (For further information, see the
Radio Programming and Commissioning Manual - ref. N200-
306-00.)
NOTE: Do not run more than one interface at a time to
commission devices in an area.
LED INDICATORS AND FAULT DESCRIPTION
The radio gateway has two LED indicators that show the status of
the device (see table below).
LED State
Long Green pulse
3 Green blinks
Blink Amber every 1s.
Red/Green double-blink every 14s
(or just Green when communicating).
Green/Amber double-blink every 14s
(or just Green when communicating).
Controlled by panel; can be set to Red
ON, periodic blink Green or OFF.
Amber/Green double-blink every 14s
EN54-18: 2005 / AC: 2007 Input/Output Devices
for use in fire detection and fire alarm systems for buildings
In accordance with EN60950 and 1999/5/EC R&TTE Directive
This product complies with the following Directive(s):
2004/108/EC Electromagnetic Compatibility
The full DoC can be obtained from Notifier by Honeywell
Meaning
Device is un-commissioned
(factory default)
Device is commissioned
Device has an internal trouble
Device is powered and is waiting to be
programmed.
Device is powered, programmed and
trying to find/join the RF network.
RF communications is established;
device is working properly.
Commissioned RF network is in standby;
used when the gateway is powered off.
0333 16
Pittway Tecnologica S.r.l.
Via Caboto 19/3, 34147 Trieste, Italy
DOP-IRF020
EN54-25: 2008 / AC: 2010 / AC: 2012
Components Using Radio Links
EC Declaration of Conformity
2006/95/EC Low Voltage
Patents Pending
I56-4208-001

Publicidad

loading