Descargar Imprimir esta página

Maintenance; Return And Disposal - Refco Combi 3004146 Guía De Instalación Y Funcionamiento

Bomba de condensados

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

English

Maintenance

Water filter maintenance
Regular cleaning / replacement of the Combi water filter will help to prolong the life of the pump. The sole purpose of the water filter is
to prevent foreign debris from entering the pump itself. The time period between filter service can only be determined from the specific
environment in which the pump is installed. We recommend cleaning or replacing the water filter a minimum of every 12 months.
However, when installed in environments with high dust, smoke, cooking oils or the possibility of algae growth it is recommended to
clean or replace the filter every 3 months.
To clean / replace the water filter, simply remove it from the water sensor body and thoroughly wash with cold water and replace in
between the two interior sensor body retaining flanges as shown below.
Change alarm fuse
1
WARNING:
Disconnect all electrical power before starting
installation, maintenance, or service work.
The alarm relay fuse must be rated for the specific application and
of the HRC type, 5 x 20 mm 250VAC, 6.3A (MAX)
Installations must only be carried out by qualified personnel.

Return and disposal

At the end of useful life of the condensate pump send the product to the separate collection for electric and electronic devices.
(According to local regulations)