Descargar Imprimir esta página

Ducting Requirements - Avanti SED67D0W Manual De Instrucciones

Publicidad

Idiomas disponibles

Idiomas disponibles

DUCTING REQUIREMENTS

Weather Hood
Type
No. of 90°
elbows
0
1
2
3
If this new dryer is installed into an existing exhaust system you must
make sure:
The exhaust system meets all local, state, and national codes.
That a flexible plastic duct is not used.
To inspect and clean all lint buildup from inside the existing duct.
The duct is not dented or crushed.
The exhaust hood damper opens and closes freely.
Manometer measurements
The static pressure in any exhaust system for best results shall be between
0.3 to 0.8 inches of water column, and cannot be less than 0 under any
circumstances. with installed duct of 4 inch diameter. Measurement must
be done with the empty dryer working with a manometer at the point
where the exhaust duct connects to the dryer. A no-heat setting should be
used. Lint filter must be clean.
Recommended
4" DIA
4" DIA
4"
4 inch. (10.2 cm)
Rigid Metallic
90 ft. (27.4 m)
60 ft. (18.3 m)
45 ft. (13.7 m)
35 ft. (10.7 m)
Use only for short-run
installation
4" DIA
2-1/2"
2.5 inch. (6.4 cm)
Rigid Metallic
60 ft. (18.3 m)
45 ft. (13.7 m)
35 ft. (10.7 m)
25 ft. ( 7.6 m)
12

Publicidad

loading

Este manual también es adecuado para:

Sgd67d0wg