Descargar Imprimir esta página

ESBE TEA117 Serie Instalación página 3

Termostato electrónico de ambiente para sistemas de calefacción

Publicidad

Idiomas disponibles

Idiomas disponibles

OVERVIEW
This device is an electronic room thermostat for
heating systems suitable for reliable and accurate
temperature regulation in commercial and industrial
premises as well as for home installation.
The room temperature can be sensed by the
internal sensor or a remote sensor (optional).
OPERATION
When the measured room temperature is below the
value set on the internal trimmer, (3) of Fig. 6, the
thermostat turns the relay on and, at the same time,
turns the red LED on.
TEMPERATURE ADJUSTMENT TRIMMER
The user can set the room temperature by moving the
internal trimmer, (3) of Fig. 6, to any desired
temperature, as explained in the former paragraph,
between 6°C and 30°C.
INSTALLATION
a
WARNING
- To adjust properly room temperature, install
the thermostat about 1.5m from floor level, far
from heat sources, airstreams or particularly
cold walls (thermal bridges). When the remote
sensor is used in conjunction with the
thermostat, then this note is to be applied to
the remote sensor itself.
- For remote version all wirings must be made
using wires with 1,5 mm² minimum cross
section and no longer than 25 m. Do not use
same duct for signal wires and mains.
- The appliance must be wired to the electric
mains
through
a
switch
capable
disconnecting all poles in compliance with
the current safety standards and with a
contact separation of at least 3 mm in all
poles.
- Installation and electrical wirings of this
appliance
must
be
made
by
qualified
technicians and in compliance with the
current standards.
- Before wiring the appliance be sure to turn
the mains power off.
For installation the thermostat follow these steps:
1. Remove plastic cover by moving to the inner
side, through the use of a tool (Fig. 4), the two
plastic teeth (2) located on the left side of the
thermostat.
2. Fix the thermostat base plate to the wall through
the two screw holes with distance between axes
of 60 mm (Fig. 2).
3. Make the electrical connections, routing the wires
through the rectangular opening (5) and following
to the diagram of Fig. 5.
4. Close the thermostat by carefully positioning the
cover so that the LED matches the relevant hole
and then by slightly pressing the cover in order to
make the four plastic teeth snapping. Then insert
the knob.
SELECTION INTERNAL/EXTERNAL SENSOR
The thermostat leaves the factory configured by
default for operation with the internal temperature
sensor.
If it is planned to install a remote sensor, remove
the jumper connector JP1 (4 of Fig. 6) and connect
an NTC type sensor (4700 ohm@ 25°C) with a
suitable beta value to terminals 7 and 8. In case of
doubt as to the type of sensor to connect, please
consult the manufacturer.
TECHNICAL FEATURES
Power supply:
230V~ -15% +10% 50Hz
Power absorption:
5,3VA
Regulation range:
6°C .. 30°C
Differential:
0,5°C
Internal sensor type:
NTC 4,7kΩ @ 25°C
Remote sensor optional: NTC 4,7kΩ @ 25°C
(optional)
Contact rating:
5 (1) A @ 250V~ SPDT
Protection grade:
IP 30
Operating temperature: 0°C .. 40°C
Storage temperature:
-10°C .. +50°C
Humidity limits:
20% .. 80% RH
(non condensing)
Case:
Material:
ABS self extinguishing V0
Color:
Signal white (RAL 9003)
Size:
85 x 85 x 31 mm (W x H x D)
Weight:
~135 gr.
CLASSIFICATION UNDER REG. 2013.811.EC
Class:
I
Contribution to energy efficiency: 1%
of
NORMATIVE REFERENCES
The product complies with the following standards
(EEC 2004/108/c and 2006/95/c):
EN-60730-1 (2011)
EN-60730-2-9 (2010)
WARRANTY
The manufacturer is committed to the continual
development of its products and hence reserves the
right
to
change
technical
specifications
performance features without notice. Consumers are
provided with a warranty against product non-
conformity in accordance with European Directive
1999/44/EC and the manufacturer's guarantee policy.
The complete text of the warranty is available on
request from the seller.
3
- ENGLISH -
and

Publicidad

loading