Messag
e
0x01
exampl
e
The meter has 30 alarm event records, and judges and processes voltage, current,
power, etc. every 1s. Record the time and type of the event. Thresholds and hysteresis
for voltage, current, power, etc. are set through communication.
Alarm event record data format description:
Year, month, day, hour, minute, second (6byte) + spare byte (2byte) + alarm type
(2byte) + spare byte (6byte)
Year, month, day, hour, minute, second: the time when the alarm event occurred.
Alarm Type: Alarm event type.
For example:0x0E 0x03 0x05 0x08 0x14 0x01 0x00 0x00 0x00 0x02 0x00 0x00 0x00
0x00 0x00 0x00
0x0E 0x03 0x05 0x08 0x14 0x01:Indicates the time at 8:20:1 on March 5, 2014.
0x00 0x00:spare byte
0x00 0x02:A phase current high alarm
0x00 0x00 0x00 0x00 0x00 0x00:spare byte
Alarm event number (part)
0. High frequency
1. Low frequency
2. High phase A current
3. A phase current is low
SAM3001 Manual de usuario V5
0x14
0x12
-103-
0x11
0x06
Alarm
record
CRC16
data