I Front view with operating controls
a Adjustment of the time range (depending on the device)
by selecting the max. value of the desired time range:
Time range:
0.05 - 1 s
=
0.5 - 10 s
=
5 - 100 s
=
0.5 - 10 min
=
5 - 100 min
=
0.5 - 10 h
=
5 - 100 h
=
b Direct reading scale to set the time value within the
chosen range
Calculation of the time value:
"Range"
1 s
10 s, 10 m, 10 h
100 s, 100 m, 100 h
Example 1:
Time value to set: 0.5 s
Select 1 s on scale "Range"
Select 5 on scale "Time"
5 x 0.1 = 0.5 s
Example 2:
Time value to set: 80 s
Select 100 s on scale "Range"
Select 8 on scale "Time"
8 x 10 = 80 s
c Function on CT-AHD, CT-EBD, CT-ERD, CT-VWD /
Selection of the function on CT-MFD
Functions: see III
d Indication of operational states with LEDs
U: green LED
R/R1/R2: yellow LED - Status indication of output relays
e Adjustment of the transition time on CT-SAD
II Wiring notes for devices with control input
A parallel load to the control input is possible / allowed
Electrical connection
For the rated control supply voltage and the
circuit diagram, see label at the side of the unit.
A1-A2
Control supply voltage Us
A1-Y1/B1
Control input to start timing
(voltage-related triggering)
15-16/18
1st c/o contact
25-26/28
2nd c/o contact
17-18
1st n/o contact
17-28
2nd n/o contact
Scale:
1 s
10 s
100 s
10 m
100 m
10 h
100 h
Value on scale "Time"
x 0.1= Time value
x 1 = Time value
x 10 = Time value
- Status indication of control supply
voltage and timing
Control supply voltage
V
applied
Time delay is running
W
1 and 2
energized
V
III Function diagrams
CT-AHD
2 B
OFF-delay with auxiliary voltage
t
adjusted time delay
CT-EBD
5 DA
Flasher, starting with ON
t
adjusted flashing time
CT-ERD
1 A
ON-delay
t
adjusted time delay
CT-MFD
1 A
ON-delay
t
adjusted time delay
2 B
OFF-delay with auxiliary voltage
t
adjusted time delay
3 CA Impulse-ON
t
adjusted pulse time
4 CB Impulse-OFF with auxiliary voltage
t
adjusted pulse time
5 DA
Flasher, starting with ON
t
adjusted flashing time
6 DB
Flasher, starting with OFF
t
adjusted flashing time
7 H
Pulse former
t
adjusted pulse time
CT-SAD / CT-SDD
9 F
Star-delta change-over
t1 adjusted starting time
t2 transition time
CT-SAD: t2 = adjustable
CT-SDD: t2 = 50 ms
CT-TGD
8 ED
Pulse generator, starting with ON or OFF
t1 adjusted OFF time
t2 adjusted ON time
CT-VWD
3 CA Impulse-ON
t
adjusted pulse time
Legend
LED
Green LED flashes whilst timing
A1-A2
Control supply voltage U
A1-Y1/B1
Control input (voltage-related triggering)
15-16/18
1st c/o contact
25-26/28
2nd c/o contact
17-18
1st n/o contact
17-28
2nd n/o contact
Control supply voltage not applied /
G
output contact open
Control supply voltage applied /
B
output contact closed
English