EN
Complete instruction guide available online on www.somfy.com/projects
Before installation, please read and follow these instructions. Incorrect installation may lead to serious injury. Disconnect
all power cables to be installed! Take precautions against unintentional switching on! The product must be installed,
maintained and dismounted by a skilled person according to the relevant regulation. An all-pole mains switch shall be in-
corporated in the electrical installation of the building to provide simultaneous separation of at least 3 mm for all phases
from the supply.
Somfy cannot accept any liability for defects and damage caused by failure to follow these instructions. Please keep
these instructions for future reference.
SOMFY hereby declares that this product is in compliance with the essential requirements and other relevant provisions
of the European Directives applicable to the European Union. A declaration of conformity is available at
www.somfy.com/ce.
Somfy limited, Yeadon LS19 7ZA UK, hereby declares that the radio equipment covered by these instructions is in com-
pliance with the requirements of UK legislation: the Radio Equipment Regulations S.I. 2017 N°1206. The full text of the
UKCA declaration of conformity is available at www.somfy.co.uk
A
MOUNTING
Mounting in electrical cabinet, false ceiling, floor or wall
mounting. Ensure that the unit is mounted on a solid sur-
face to guarantee safety and a secure fixing of the unit.
The unit shall be mounted in such a way, that the back
side is not accessible.
[1] Choose the optimum location: flat and large surface.
[2] Select the relevant screws according to the material
of the mounting site and mount the animeo Power
Supply DC. Mains connection should not be accessi-
ble following correct installation.
CHARACTERISTICS
Supply voltage
Stand-by current (IEC 62301)
Stand-by power (IEC 62301)
DC output@24 V DC (100 %)
DC output@24 V DC (ED 50 %)
Terminals
Operating temp.
Relative humidity
Material of housing
Housing dimensions
Weight
Degree of protection
Conformity
CABLES
Connection to ...
220 - 240 V AC
24 V DC
We care about our environment. Do not dispose of the appliance with usual household waste. Give it to an ap-
proved collection point for recycling.
8/20 -
animeo Power Supply DC Ref. 5010767E
Cable
Min.: 2 x 1.5 mm²/15 AWG
Max.:2 x 2.5 mm²/13 AWG
Min.: 2 x 1.5 mm²/15 AWG
Max.:2 x 2.5 mm²/13 AWG
[3] Use cable tie!
B
WIRING
[1] Tool for all terminals
[2] Wiring diagram
C
MAX. OUTPUT CURRENT
[1] 2.5 A (100 % permanent),
4.5 A (intermittent operation t
220 - 240 V AC / 50/60 Hz ~
45 mA@230 V/50 Hz
1.8 W@230 V/50 Hz
2.5 A
4.5 A
Spring connectors
0° C ... 45° C
Max. 85 %
PC-ABS
130 x 180 x 62 mm
460 g
IP20
www.somfy.com/ce
Temperature resistance
+ 90° C
3 min./t
3 min.)
on
off
Max. distance
10 m/33 ft