8. Specifications
8. Specifications
Compact temperature transmitter, model TFT35
Output signals
Accuracy
Measuring element
■
Electronics
■
Power supply U
B
Max. permissible residual
ripple
Error signalling
Sensor break
■
Sensor short-circuit
■
Electromagnetic
compatibility (EMC)
Thermowell
Material
Static operating pressure
1) Use temperature transmitters with shielded cable, and, if the lines are longer than 30 m or leave
the building, ground the shield on at least one end of the lead.
WIKA operating instructions model TFT35
4 ... 20 mA
0 ... 10 V
±(0.3 + 0.005 * t) °C (class B per IEC 60751)
±0.5 % of measuring span
Overall accuracy = accuracy of measuring
element + accuracy of electronics
Example:
Medium temperature t = 150 °C
Measuring range 0 ... 200 °C
→ ±(0.3 + 0.005 * 150) + 0.5/100 * 200 = ±2.05 °C
DC 10 ... 30 V
DC 12 ... 30 V
< 10 %
< 10 %
> 20.5 mA
> 10.5 V
< 3.8 A
0 V
EN 61326 emission (group 1, class B) and
immunity (industrial application)
Stainless steel
Max. 40 bar
For higher pressures, please speak to a WIKA
contact person
0.5 ... 4.5 V,
ratiometric
DC 5 V
< 10 %
> 4.5 V
0 V
1)
21
EN