Commissioning and adjustment
2.
A Setting wheel
2. Test the contact humidistat:
Using a screwdriver, turn the setting
wheel anti-clockwise or clockwise
until you hear a clicking sound
(switching point).
3. Set the switching point:
Turn the setting wheel to the
required switching point with the
screwdriver.
Select a switching point that will not
allow any condensate to form on
the cooling surfaces.
Recommended setting: ≤ 80 %.
16
A
4. Close the heat pump and switch
on the power supply:
1.
Heat pump installation and
service instructions