I Front view with operating controls
Adjustment of the time range by selecting the max. value:
Range
Max. value
0.15 - 3 s
>> 3 s
1.5 - 30 s
>> 30 s
15 - 300 s
>> 300 s
1.5 - 30 min
>> 30 min
15 - 300 min
>> 300 min
1.5 - 30 h
>> 30 h
15 - 300 h
>> 300 h
0.05 - 1 s
>> 1 s
0.5 - 10 s
>> 10 s
5 - 100 s
>> 100 s
0.5 - 10 min
>> 10 min
Direct reading scale to set the time value within the chosen
range
Selection of the function on 700-FSM6, 700-FSM7, 700-FSM8
Functions: see III
Indication of operational states with LEDs
U/T: green LED
- Status indication of control supply
voltage and timing
V
W
R: yellow LED
- Status indication of output relay
V
R1/R2: yellow LED - Status indication of output relays
1 and 2
V
II Electrical connection
For the rated control supply voltage and the circuit
diagram, see label at the side of the unit.
A1-A2
Control supply voltage U
A1-B1
Control input (voltage-related triggering)
15-16/18
1st c/o contact
25-26/28
2nd c/o contact
17-18
1st n/o contact
17-28
2nd n/o contact
700-FSQ6, 700-FSQ7:
Prior to first commissioning and after a storage time of more than 6
months without any voltage, a formatting time of about 5 minutes is
necessary!
Only after applying the control supply voltage for the first time will the
output contacts take their correct switching position.
yellow
dial
white
dial
Control supply voltage applied
Time delay is running
energized
energized
s
III
Functions
700-FSA6, 700-FSA7
A
ON-delay
t
adjusted time delay
700-FSB6, 700-FSB7
B
OFF-delay with auxiliary voltage
t
adjusted time delay
700-FSK6
K
One shot with B1
t
adjusted time delay
700-FSM6, 700-FSM7
A
ON-delay
t
adjusted time delay
A+
Accumulative ON-delay
t
adjusted time delay
B
OFF-delay with auxiliary voltage
t
adjusted time delay
C
ON-delay and OFF-delay, symmetrical
t1 adjusted ON-delay
t2 adjusted OFF-delay
D
Impulse-ON
t
adjusted pulse time
E
Impulse-OFF with auxiliary voltage
t
adjusted pulse time
FG Flasher, starting with ON or OFF
t
adjusted flashing time
L
Pulse former
t
adjusted pulse time
T
ON/OFF-function
OFF-Function: Time sector = 300 h
Y1
Star-delta change-over with impulse function
(not on 700-FSM6UU23)
t1 adjusted starting time
t2 fixed transition time of 50 ms
700-FSM8
A
ON-delay
t
adjusted time delay
D
Impulse-ON
t
adjusted pulse time
F
Flasher, starting with ON
t
adjusted flashing time
G
Flasher, starting with OFF
t
adjusted flashing time
I
Fixed impulse with adjustable time delay
t1 adjusted time delay
t2 fixed pulse time of 500 ms
M
Adjustable impulse with fixed time delay
t1 adjusted pulse time
t2 fixed time delay of 500 ms
T
ON/OFF-function
OFF-Function - time sector = 300 h
700-FSQ6, 700-FSQ7
Q
OFF-delay without auxiliary voltage
t
adjusted time delay
700-FSY7
Y
Star-delta change-over
t1 adjusted starting time
t2 fixed transition time of 50 ms
Legend
t3
Pause timing
LED
Green LED flashes whilst timing
Control supply voltage not applied /
G
output contact open
Control supply voltage applied /
B
output contact closed
English
6