Quick Start Guide
English
CTV 210-R
Air velocity and temperature
transmitter
Airflow function
2 relay outputs
General features
Power supply
Output
Common mode voltage <30 Vac. Maximum load: 500 Ohms (0/4-20 mA). Minimum load: 1 K Ohms (0-5/10 V)
Relay outputs
Galvanic isolation
Consumption
Electrical connection
Screw terminal block for cable 2.5 mm². Carried out according to the code of good practice
PC communication
Environment
Conditions of use (°C/%RH/m)
Storage temperature
Security
European directives
Features of the housing
Material
ABS V0 as per UL94
Protection
IP65
75 x 40 mm, LCD 20 digits 2 lines.
Display
Height of digits: Values: 10 mm;
Units: 5 mm
Cable gland
For cables Ø 8 mm maximum
Weight
340 g
Two 4-wire analogue output
0-5/10 V or 0/4-20 mA
0-5 / 10 V
4-20 mA
ABS V0 IP65 housing,
optional display
24 Vac / Vdc ±10%. 100-240 Vac, 50-60 Hz
Warning: risk of electric shock
2 x 4-20 mA or 2 x 0-20 mA or 2 x 0-5 V or 2 x 0-10 V (4 wires)
2 changeover relays 3 A / 230 V. NO : 5A / NC: 3A / 240 Vac
Inputs and outputs (models 100-240 Vac). Device fully protected by
DOUBLE ISOLATION or REINFORCED ISOLATION
Outputs (models 24 Vac/Vdc)
CTV210-B: 6 VA. CTV210-H: 8 VA
USB-Mini Din cable
Air and neutral gases
From -10 to +50 °C. In non-condensing condition. From 0 to 2000 m.
From -10 to +70 °C
Protection class II; Pollution degree 2; Overvoltage category 2 (OVCII)
2014/30/EU EMC; 2014/35/EU Low Voltage; 2011/65/EU RoHS II; 2012/19/EU WEEE
All dimensions are in millimeters.
59
125
Used symbols
For your safety and in order to avoid any damage of the device, please follow the procedure described in
this document and read carefully the notes preceded by the following symbol:
The following symbol will also be used in this document, please read carefully the information notes
indicated after this symbol:
Connections
1
4
3
2
2
7
CTV210-XXX-S-R
CTV210-XXX-S-R
Power supply: 100-240 Vac
Power supply: 24 Vac/Vdc ±10 %
Power supply type (b) specified on the label
50-60 Hz 8 VA
50-60 Hz 6 VA
on the side of the transmitter
Output: 0/4...20 mA / 0...5/10 V
Output: 0/4...20 mA / 0...5/10 V
100-240 Vac
24 Vac/Vdc
(a)
(c)
or
(c)
Analogue output 1
Analogue output 2
For 24 Vdc power
For 24 Vac power
(out 1)
(out 2)
supply models
supply models
-
Neutral (N)~
+
Phase (L)~
NO: normaly opened
COM: common
NC: normaly closed
*Fuse present only for 100-240 Vac models.
Every fuse replacement must be performed witht a power off device using a TR5 630 mA 250 V fuse.
Electrical connections as per NFC15-100 standard
This connection must be made by a formed and qualified technician. To make the connection, the transmitter must not
be energized. Before making the connection, you must first check the power supply indicated on the transmitter board
(see (b) on "Connections" part). The presence of a switch and a circuit breaker upstream the device is compulsory.
For transmitters with 24 Vdc power supply:
The selection of the output signal in voltage (0-10 V or 0-5 V) or in current
(4-20 mA or 0-20 mA) is made via the DIP switch (d) of the electronic board
-
N-
of the transmitter: put the on-of switches as shown in the table below:
24 Vdc
Power supply
L+
+
Configurations
For transmitters with 24 Vac power supply:
24 Vac power supply
class II EN61558-2-6 standard
Combinations
N
N-
Pe
N
230 Vac
L
L+
L
Connection of the output in current
or
4-20 mA:
Pe
N
N-
230 Vac
N
L
L+
L
Power supply
For transmitters with 100-240 Vac power supply:
Regulator display or
N
PLC/BMS passive type
N-
100-240 Vac
Power supply
L+
L
On 100-240 Vac models, if a fuse protection is used for the power line, it is imperative to use delayed-action
fuses in order to absorb the surge of current when first turned on the transmitter.
1.
DIP switch (d)
2.
LCC-S software connection
5
3.
Relays
4.
Analogue outputs (a)
6
5.
F3.20* fuse
6.
Power supply terminal block (c)
7.
Cable glands
or
(c)
For 100-240 Vac
power supply models
Operating grounding
Neutral (N)~
Phase (L)~
Relays 1 and 2
4-20 mA
0-10 V
0-5 V
0-20 mA
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
Connection of output in voltage
0-10 V:
0-5/10 V
0/4-20 mA
0-5/10 V
0/4-20 mA
-
+
+
-
A
V
Regulator display or
PLC/BMS passive type
4-20 mA output
0-10 V output