Operation Modes
MODE
Status LED (Top)
Power Up
Blink Green once
Normal (Standby)
----
CO Alarm
Blink Red every 10 seconds
CO Alarm Silence
Blink Red every 8 seconds
FUNCTIONAL TESTING
CANNED CO NOTE: Detector sounds an alarm when using canned CO only when in Functional Test mode
(canned CO does not cause alarm sounding when in normal mode).
Product must be tested at least once each year
*
Use UL/ANSI Approved canned CO.
PERIODIC CLEANING
NOTE: Notify the proper authorities that the CO detector is undergoing maintenance and the system will
temporarily be out of service.
BATTERY REPLACEMENT
Caution: The battery used in this device may present a fire or chemical burn hazard if mistreated. Do not recharge,
disassemble, heat above 212°F (100° C) or dispose of in fire. Use only Panasonic CR123A Lithium batteries. Use of
other batteries may present a risk of fire or explosion. Keep used batteries away from children. Dispose of used
batteries properly.
Remove old battery. Wait 10 seconds and then replace with new battery.
NOTE: Constant exposure to high or low temperature or high humidity may reduce battery life.
NOTE: Batteries available at your local retailer or distribution center.
LED Indication & Sounder During Test and Trouble
MODE
Status LED (Top)
CO Test
1
Blink Red during alarm
Functional CO Test
1
– Waiting
Blink Green once every second
for gas entry
Functional CO Test - Successful
Blink Red every 10 seconds
gas entry
Blink Amber every
Low Battery
45 seconds
Double Blink Amber every 8
CO Trouble
seconds
Double Blink Amber every 4
CO End of Life
2
- First 29 days
seconds
Double Blink Amber every 4
CO End of Life
- After 30 days
2
seconds
1
Test activated by pressing and releasing the
CO TEST/HUSH
Functional Test section for Functional Test activation and procedure. If Test mode is activated and the LED and Sounder do not
function, check for maintenance or trouble conditions.
2
Starts chirping after 30 days, continues until the battery is replaced or dies.
SPECIFICATIONS / ESPECIFICACIONES
Battery / Bateria: ............................................................................................................................................. 1 x 3V, CR123A Lithium/Litio; Panasonic CR123A only / Panasonic CR123A solamente
Audible Signal / Señal audible: ......................................................................................................................................................................................................................................................85dBA
Dimensions / Dimensiones: ................................................................................................................................................... 6.2 in. Diameter x 1.99 in. Depth / 157mm Diámetro x 50mm Profundidad
Weight / Peso: ..................................................................................................................................................................................................................................... 14.3 oz; 406 g / 14,3 oz; 406 g
Tamper / interruptor de anti-sabotaje: ........................................................................................................................................................................................................................... Cover / Cubierta
Operating Temperature / Temperatura de funcionamiento: ................................................................................................................................................................................................................. 32° to 100° F / 0° a 38° C
Storage Temperature / Temperatura de almacenamiento: .............................................................................................................................................................................. 14° to 158° F / -10° a 70° C
Relative Humidity / Humedad relativa: ............................................................................................................................................................. 95% max, non-condensing / 95% max, sin condensado
R800-26838A 6/21 Rev. A Part 1
LED Windows
Sounder
(Side)
Dark
Silent
Dark
Silent
Blink Blue
Temp-4
Blink Blue
Silent
Side LED Windows
Sounder
Dark
Temp-4 (two times)
Dark
Silent
Blink Blue every 10
Temp-4
secs
Chirps every 45
Dark
seconds after 7 days
Dark
Silent
Dark
Silent
Chirp every 45
Dark
seconds
button; Detector is functioning properly (within proper sensitivity). See
MODO
Encendido
Parpadeo verde una vez
Estado normal
---
Alarma de monóxido de carbono
Parpadeo rojo cada 10 segundos
Silencio de alarma de monóxido
Parpadeo rojo cada 8 segundos
de carbono
PRUEBAS FUNCIONALES
NOTA ACERCA DEL CO ENLATADO: Cuando se utiliza CO enlatado, el detector envía una alarma sonora solo
cuando se encuentra en modo de prueba funcional (el CO enlatado no activa el sonido de la alarma cuando el
detector está en modo normal).
El producto debe ser probado al menos una vez al año
* Use envases de CO aprobados por UL/ANSI
LIMPIEZA PERIÓDICA
NOTA: Notifique a las autoridades correspondientes que el detector de CO está en mantenimiento y que el
sistema permanecerá temporalmente fuera de servicio.
CAMBIO BATERÍA
¡Precaución! las batería utilizadas en este dispositivo pueden generar un peligro de incendio o quemadura
química si no son tratadas adecuadamente. No recargue, desarme, caliente a más de 100°C (212° F) o arroje al
fuego. Use solamente baterías de litio Panasonic CR123A. Cuando instale las nuevas baterías, El uso de otras
baterías puede presentar un riesgo de incendio o explosión. Mantenga las baterías usadas lejos del alcance de
los niños. Descarte apropiadamente las baterías usadas.
Extraiga las batería viejas. Espere 10 segundos y luego reemplace con batería nueva.
NOTA: Exposición constante a altas o bajas temperaturas o alta humedad puede reducir la vida útil de la pila.
NOTA: Baterías disponibles en su punto de venta local o centro de distribución
Indicación LED y Sonidor Durante Pruebas y Problemas
MODO
Prueba de alarma de monóxido
Parpadeo en rojo durante la
de carbono
1
alarma
Prueba funcional de monóxido de
Parpadeo verde una vez cada
carbono – esperando por prueba
Segundo
de gas
1
Prueba funcional de monóxido
de carbono – prueba de gas
Parpadeo rojo cada 10 segundos
exitosa
Parpadeo color ámbar cada 45
Batería baja
segundos
Problema con de monóxido de
Doble parpadeo
carbono
cada 8 segundos
Final de vida de monóxido de
Doble parpadeo color ámbar
carbono– Primeiros 29 dias
2
cada 4 segundos
Final de vida de monóxido de
Doble parpadeo color ámbar
carbono – após 30 dias
2
cada 4 segundos
1
Prueba activada por el
botón
de
CO
TEST/HUSH; El detector está funcionando correctamente (Dentro de la sensibilidad
adecuada). Consulte la sección Prueba funcional para la activación y el procedimiento de la prueba funcional). Si se activa el
modo de prueba y ni el led ni la sirena funcionan, verifique el mantenimiento o las condiciones problema.
2
Comienza el chirrido después de 30 días y continúa hasta la batería son cambiadas o se agotan.
Modos de Operación
Ventana del LED
Estado del LED
(Lateral)
Apagado
Apagado
Parpadeo azul
Parpadeo azul
Ventana del LED
Estado del LED
(Lateral)
Apagado
Apagado
Parpadeo azul cada
10 segs
Apagado
color ámbar
Apagado
Apagado
Apagado
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
© 2021 Resideo Technologies, Inc.
www.resideo.com
Sonidor
Silencio
Silencio
Tempo.-4
Silencio
Sonidor
Temp.-4 (dos veces)
Silencio
Temp.-4
Un chirrido cada 45
segs después de 7
días
Silencio
Silencio
Un chirrido cada 45
segundos

Publicidad

loading