Manual Motor
Controllers
KTA5-32A-0.16A
KTA5-32A-0.25A
KTA5-32A-0.40A
KTA5-32A-0.63A
KTA5-32A-1.0A
KTA5-32A-1.6A
KTA5-32A-2.5A
KTA5-32A-4.0A
KTA5-32A-6.3A
KTA5-32A-10A
KTA5-32A-12A
KTA5-32A-16A (1)
KTA5-32A-20A
KTA5-32A-25A (2)
KTA5-32A-25A (2)
KTA5-32A-32A (3)
(1) Limited to 15.5 FLA maximum when used in a 365 mm x 235 mm x 140 mm (200 %) or larger enclosure.
Limited to 14.5 FLA maximum when used in 115 mm x 290 mm x 180 mm (150 %) minimum sized enclosure.
(2) Minimum enclosure size is 170 mm x 670 mm x 235 mm (250 %) at full load current.
If end use current is 22.5 FLA or less, may be used in an enclosure as small as 115 mm x 290 mm x 180 mm (150 %).
(3) May be used at 30.8 FLA maximum when used in surrounding air of 40 Deg C maximum.
May be used up to 29 FLA when used in a 115 mm x 290 mm x 180 mm (150 %) minimum size enclosure.
(4) KT5-32-PEC23 connection modules may be used with CA7-09 thru -23 up to 24A.
Publication KTA5-IN001B-EN-E - March 2021
Type 1 Coordination SCCR
Contactors
480 Vac
(4)
[A]
30,000
30,000
30,000
30,000
CA7-09
30,000
CA7-12
CA7-16
30,000
CA7-23
30,000
18,000
18,000
18,000
CA7-12
CA7-16
18,000
CA7-23
CA7-16
18,000
CA7-23
CA7-23
CA7-30
18,000
CA7-37
CA7-23
18,000
CA7-30
18,000
CA7-37
CA7-30
18,000
CA7-37
Installation instruction for Manual motor starter
600 Vac
[A]
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
–
5,000
5,000
DIR 10004508030 (Version 02)
5/8
Maximum Fuse
or Circuit Breaker
sized per NEC [A]
175
175
175
175
175
175
175
175
175
175
175
175
400
400
400
400