Wiring
Notes
All wiring is supervised and power-limited.
Before connecting the amplifier to the output wiring, test
the field wiring.
Terminal blocks indicate the polarity for normal monitoring
of the circuit's electrical integrity.
Use a power-limited and regulated 24 VDC primary or
auxiliary power supply that is UL/ULC Listed for fire
protective signaling systems. See "Specifications" for
active amplifier power requirements.
To connect the amplifier field wiring:
1.
Connect the audio wiring to TB1 and TB2.
See Figure 2 for typical 1 VRMS and 25 VRMS wiring.
See Figure 3 for an example of typical backup wiring for a
1 VRMS application.
2.
Connect signaling line circuit (SLC) wiring to TB3.
3.
Connect audio riser wiring to TB4 and TB5. See Figure 3.
4.
Connect auxiliary power wiring to TB6. See Figure 3.
5.
Adjust the amplifier gain per control panel instructions.
See Figure 1 for the gain potentiometer location.
Figure 2: Typical input wiring for 1 VRMS and 25 VRMS
(1)
(2)
+
(3)
(1) Channel 1 alert audio IN from the audio source output
(2) EVAC audio IN from the audio source output
(3) Signaling line circuit (SLC) IN
2 / 14
1 VRMS
+
(4)
(5)
(6)
Specifications
Voltage
24 VDC
Current
Standby
2 mA at 24 V
Active SIGA-AA30
1.55 A at 24 V full load
Active SIGA-AA50
2.80 A at 24 V full load
Ground fault impedance
≤ 0.1 Ω or less
Frequency response
400 Hz to 4 kHz at −3 dB (ULC)
800 Hz to 2.8 kHz (ULI)
Harmonic distortion
< 5%
Input
Channel 1 dual input
1 VRMS or 25 VRMS maximum
Channel 2 dual input
1 VRMS or 25 VRMS maximum
Output
SIGA-AA30
30 watts at 25 VRMS or 70 VRMS
SIGA-AA50
50 watts at 25 VRMS or 70 VRMS
Configuration
Class B (Style Y) or Class A (Style Z)
EOL resistor
47 kΩ
Compatible enclosures
2-WB3(R), 2-WB7(R), RACCR, APS6A,
APS10A
Compatible power sources PS10-4B, BPS6A, BPS10A, APS6A,
APS10A, SIGA-APS (for retrofit only)
Signature Data Circuit
Addresses
2 module addresses
Emulation
Signature series CC2 module
Maximum wire size
12 to 18 AWG (0.75 to 2.5 mm²)
Backup tone
1 kHz
Operating environment
Temperature
32 to 120°F (0 to 49°C)
Relative humidity
0 to 93%, noncondensing
(1)
(2)
+
(3)
(4) SLC OUT
(5) Alert audio OUT
(6) EVAC audio OUT
P/N 387343-ML • REV 08 • ISS 13MAR17