Descargar Imprimir esta página

Eaton DIN500AC Guia Del Usuario página 21

Ocultar thumbs Ver también para DIN500AC:

Publicidad

Idiomas disponibles

Idiomas disponibles

C C h h a a p p t t e e r r 7 7 S S p p e e c c i i f f i i c c a a t t i i o o n n s s
7 7 . . 1 1
P P r r o o d d u u c c t t S S p p e e c c i i f f i i c c a a t t i i o o n n s s
INPUT
Breaker
Table 5. Input Characteristics
Capacity VA/Watts
Voltage AC
Frequency
Harmonic Distortion
Table 6. Output (Backup Mode)
Voltage VAC
Frequency
Transfer Time
Table 7. Protection Characteristics
Unit Input (Internal)
Overload Protection
Varistor
Bridge
Ac to DC
UPS shutdown in battery mode if overload exceeds 105% of nominal at 20s, 120% at
Battery DC Boosted
DC to Step
to High DC
Sine Wave
Level
DIN500AC
500/300
120 V + 20%, -25%
50 or 60 Hz, +/ -10% (auto-sensing)
THD: 42.1%; maximum single harmonic distortion of: 25.6%
DIN500AC
Simulated sine wave
120V +/-5%
50 or 60 Hz, +/-0.5% auto-sensing
Typical <8 ms.
DIN500AC
10A
10s, 130% at 3s; auto-recovery
Eaton Din Rail UPS Advanced User Guide 9340AC—Rev A
UPS Ouput Relay
AC
DIN850AC
850/510
DIN850AC
DIN850AC
10A
17

Publicidad

loading

Este manual también es adecuado para:

Din850ac