Initial start-up
7.12
Filling up the internal refrigerant container
I
NOTE
The A/CServiceCenter analyses the purity level of the refrigerant. If it is
below 95 %, the unit does not accept the refrigerant. The contaminated
mixture must be disposed of externally.
When the A/CServiceCenter is started for the first time, the internal refrig-
erant vessel must be filled from an external refrigerant vessel with at least
2000 g of refrigerant.
The unit displays error message 12.
Press STOP to confirm.
I
NOTE
Note the instructions on the refrigerant vessels.
Vessels for the R-1234yf refrigerant have a left-hand thread!
The current supply quantities are displayed in the standby menu.
There are three different types of refrigerant vessel available:
Refrigerant vessels without rising pipe:
These refrigerant vessels have one connection.
When filling the A/CServiceCenter, the connection must be on the
bottom (turn the vessel upside down).
Refrigerant vessels with rising pipe:
These refrigerant vessels have one connection.
When filling the A/CServiceCenter, the connection must be at the top
(place the vessel).
Refrigerant vessels with rising pipe:
These refrigerant vessels have two connections. To top up the
A/CServiceCenter, use the connection marked with L (= liquid).
When filling the A/CServiceCenter, the connection must be at the top
(place the vessel).
1. In the basic menu, use the cursor keys or to select "Other
selections":
2. Press ENTER to confirm.
90
Short selection
Free selection
Other selections
ENTER-OK
VAS 581 001