Lights will not go to High Mode:
• Check all wire connections and verify the load and the ground wires are tightly secured.
• Make sure that the sensor is not obstructed.
• Check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor lens to simulate darkness
in the room. If the lights come ON, the setpoint needs to be adjusted. If set for minimum, more than 1 fc at the sensor of ambient
light will cause the lights to be held OFF. See the new settings section for instructions.
• If lights still do not turn ON, call 800.879.8585 for technical support.
Lights will not go into Low Mode:
• The time delay can be set from a minimum of 30 seconds to a maximum of 30 minutes. Ensure that the time delay is set to the
desired delay and that there is no movement within the sensor's view for that time period.
• To quickly test the unit operation, enable test mode and move out of the sensor's view. Lights should fade to low mode after 5 seconds.
• If lights still do not fade to Low Mode, call 800.879.8585 for technical support
Lights will not turn OFF:
• Cut Off time may be set to "None."
• Ensure that the Cut Off is set to the desired time and that there is no movement within the sensor's view for that time period when
the lights are in Low Mode.
• To quickly test the unit operation, enable test mode and move out of the sensor's view. Lights should fade to low mode after
5 seconds, and the OFF (if cut off is enabled) after 10 sec.
• If lights still do not turn OFF, call 800.879.8585 for technical support.
False Triggering may occur if the sensor is exposed to high ambient temperature conditions and the unit is set to maximum sensitivity
for PIR detection.
• If this occurs, reduce the PIR sensitivity setting from maximum to a medium point and re-check unit operation.
• If experiencing false triggering during fade down/Off, try increasing the fade time.
Lights do not turn ON:
Check for blinking red LED. If the LED blinks with long pulses, as opposed to short pulses, the sensor has reached its Hold Off setpoint
or Photocell Light Level setpoint.
Lights suddenly turn off and will not come back on:
Check for blinking red LED. If the LED blinks with long pulses, as opposed to short pulses, the sensor has reached its Hold Off setpoint
or Photocell Light Level setpoint.
I forgot my password:
Hold the reset button under the sensor lens for 15 seconds. This will reset the device to default values and allow you to assign a new password.
I can't discover the sensor on the app:
If you do not connect with the sensor for 7 days after being powered on, the radio stops broadcasting. Power cycle the sensor in order
to enable the radio.
Catalog #
FSP-311
Digital Continuous Dimming PIR Fixture Integrated Sensor with Bluetooth
FSP-L2
360° lens, up to 44' diameter at 8' height
FSP-L2-S
360° lens, up to 44' diameter at 8' height, with shroud
FSP-L3
360° lens, up to 40' diameter at 20' height
FSP-L3-S
360° lens, up to 40' diameter at 20' height, with shroud
FSP-L7
360° lens, up to 100' diameter at 40' height
FSP-L7-S
360° lens, up to 100' diameter at 40' height, with shroud
FSP-C1
Small collar, for use with FSP-L2 and FSP-L3 lenses
FSP-C2
Large collar, for use with FSP-L7 lens
Sensor is White.
TROUBLESHOOTING
ORDERING INFORMATION
Description
4

Publicidad

loading