DEFA Balancer Manual De Instalación página 17

Publicidad

1.
Mount DEFA Balancer on the DIN rail.
2.
Connect the sensor leads to DEFA Balancer. Input 1 and 2 measures L1, input 3 and 4 measures
L2, input 5 and 6 measures L3:
3.
Connect the sensors to the phases that is to be measured. Make sure the arrow on the sensor
follows the current direction.
WARNING When the power is on in the facility, the current sensors must never be
disconnected from the current reader if they are to be placed on- or removed from the
power cables.
4.
Connect power to DEFA Balancer to an existing circuit branch in the installation or a separate
circuit breaker (Max. 20A). The circuit breaker must be marked as the disconnection device for
DEFA Balancer.