WORK SAFE, READ THIS
Failure to read and comply with all warnings, cautions and instructions prior to starting
installation may cause personal injury and/or property damage and void warranty.
The AG-1250E must be installed in accordance with manufacturer's instructions. The AG-1250E
STOP/READ
must be installed in accordance with all applicable local plumbing, drainage and electrical codes.
Remove electrical shock hazard – DISCONNECT THE POWER TO THE HVAC UNIT BEFORE INSTALLING
THE AQUAGUARD AG-1250E to avoid electrical shock and/or equipment damage. Do not use on circuits
exceeding 24 VAC to avoid damage to sensor, shock or fire hazard.
In some situations the sensor may cause the unit to rapidly cycle on and off as water level
rises slowly in pan. After a brief period the HVAC unit will turn off completely. Condensation drain must be
serviced if this occurs.
In any installation where property damage and/or personal injury might result from an
inoperative sensor due to power outages, a back-up system(s) and /or alarm should be installed.
The AG-1250E must only be installed by a licensed contractor. Condensation pan must be
NOTICE
NOTICE
properly maintained after installation and be kept free of foreign matter, rust or other obstructions that
might interfere with the proper operation of the AG-1250E.
Cleaning solutions or dirty probes m ay not allow the HVAC unit to come on. If such, remove probe
NOTICE
NOTICE
sensor and/or secondary pan sensor, clean, and dry.
Wiring the AG-1250E:
NOTICE
NOTICE
To ensure proper performance of product, instructions must be followed.
the AG-1250E:
Mounting clip
1. In HVAC Unit locate HVAC Power wire going to "Wall Thermostat", (Typically RED).
Break/Disconnect 24 VAC Power wire going to "Wall Thermostat".
A. Connect "RED", "Input 24 VAC (Hot)" and "Gray" "Common" wire of AG-1250E to 24 VAC
(Hot) secondary side of 24 VAC Transformer.
B. Connect "Purple", "Normally Closed" wire of AG-1250E to Thermostat's "R" Terminal wire.
NOTE: "Purple" wire must be connected to "Thermostat". Maximum capacity
24VAC/5Amp.
C. Connect "BLACK", "Input: 24 VAC (Common)" wire of AG-1250E to 24 VAC (COMMON)
secondary side of 24 VAC Transformer or Thermostat's "C"Terminal.
D. Optional: Connect "WHITE", "Normally Open" wire of AG-1250E to the "WHITE" wire of
AquaGuard, AG-9100 External Alarm or Home Alarm System, or Communicating System,
etc...
NOTE: "WHITE", "Normally Open" wire maximum capacity, 24VAC/1Amp.
2. Test the AG-1250E Secondary Pan Sensor (At start-up check initial amperage load) while the
HVAC unit is on and functioning correctly. See installation of sensor.
NOTE: When AG-1250E is wired correctly, the HVAC unit will shut off upon condensate
detection.
1. In HVAC Unit locate Compressor wire going to "Wall Thermostat", (Typically YELLOW).
Break/Disconnect Compressor wire going to "Wall Thermostat".
A. Connect typically "YELLOW" wire, going to "Wall Thermostat" to "Gray" "Common" wires
of AG-1250E.
B. Connect "Purple", "Normally Closed" wire of AG-1250E to Compressor's typically
"YELLOW" wire going to compressor.
NOTE: "Purple" wire must be connected to Compressor "YELLOW" wire. Maximum
capacity 24VAC/5Amp.
C. Connect "RED", "Input: 24 VAC (HOT)" wire of AG-1250E to 24 VAC (HOT) of 24 VAC
Transformer or Thermostat's "R"Terminal.
D. Optional: Connect "WHITE", "Normally Open" wire of AG-1250E to the "WHITE" wire
of AquaGuard, AG-9100 External Alarm (see Figure 1.) or Home Alarm System, or
Communicating System, etc...
NOTE: "WHITE", "Normally Open" wire maximum capacity, 24VAC/1Amp.
2. Test the AG-1250E Secondary Pan Sensor (At start-up check initial amperage load) while the
HVAC unit is on and functioning correctly. See installation of sensor.
NOTE: When the AG-1250E is wired correctly, (ONLY) the Compressor unit will shut-off upon
condensate detection. Air Handler will continue to run.
Installation of sensor:
(To ensure proper performance of product, instructions must be followed)
1. Clean desired mounting surface throughly with included alcohol pad.
2. Using the adhesive tape, affix the mounting clip to the desired surface in pan. Next, snap
AG-1250E to mounting clip.
3. Place the ATTENTION sticker on HVAC unit in a clearly visible location.
4. Test sensor: Place sensor in secondary pan and add enough water to the pan to cover
contacts (approximately ¼ inch). LED will illuminate and HVAC unit will stop running if wired
correctly.
Specifications:
Relay normally closed contact 5 Amps @ 24VAC - Red to Purple; Relay normally open
contact 1 Amp @ 24VAC - Red to White.
Limited Warranty
For more information on our product
limited warranty, visit RectorSeal.com
Manufactured by
RectorSeal, LLC
2601 Spenwick Drive  Houston, TX 77055, USA  800-231-3345  Fax 800-441-0051 
A CSW Industrials Company. RectorSeal, the logos and other trademarks are property of RectorSeal, LLC, its affiliates or its licensors and are protected by copyright,
trademark and other intellectual property laws, and may not be used without permission. RectorSeal reserves the right to change specifications without prior notice.
©2023 RectorSeal. All rights reserved. R50118-0223
I N S T A L L A T I O N I N S T R U C T I O N S
AQUAGUARD
Multi-purpose electronic water sensor shut-off
Metal
contacts
Moisture detection LED
24 Volt AC, 5 Amp, GP,
Use in Class 2
(Thermostat) Circuit Only
AG-1250E
®
R50118-0223
rectorseal.com
R50118-0223

Publicidad

loading

Resumen de contenidos para RectorSeal AQUAGUARD AG-1250E

  • Página 1 A CSW Industrials Company. RectorSeal, the logos and other trademarks are property of RectorSeal, LLC, its affiliates or its licensors and are protected by copyright, trademark and other intellectual property laws, and may not be used without permission. RectorSeal reserves the right to change specifications without prior notice.
  • Página 2 A CSW Industrials Company. RectorSeal, the logos and other trademarks are property of RectorSeal, LLC, its affiliates or its licensors and are protected by copy- right, trademark and other intellectual property laws, and may not be used without permission. RectorSeal reserves the right to change specifications without prior notice.