Descargar Imprimir esta página

Hitachi YUTAKI M Manual De Instalación Y Funcionamiento página 17

Ocultar thumbs Ver también para YUTAKI M:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 19
ELECTRICAL AND CONTROL SETTINGS
!
C A U T I O N
Never turn all DSW4 dip switch pins ON. If this happens, the software
of the unit will be deleted.
Never activate "Heater Forced OFF" and "Electric heater or boiler
emergency mode" at the same time.

DSW5: Additional setting 3
In the cases where the outdoor unit is installed into a location
where its own outdoor ambient temperature sensor can not
give a suitable temperature measurement to the system, it
is available the 2nd outdoor ambient temperature sensor as
accessory. By means of DSW1&2 setting, the preferable sensor
for each circuit can be selected.
Factory setting
Outdoor unit sensor for circuits 1 and 2.
Outdoor unit sensor for circuit 1; Auxiliary
sensor for circuit 2.
Auxiliary sensor for circuit 1; Outdoor unit
sensor for circuit 2.
Auxiliary sensor instead of outdoor unit
sensor for both circuits.
Use the maximum temperature value
between Two3 (boiler / heater thermistor) and
Two (water outlet thermistor) for water control

DSW6: Not used
Factory setting
(Do not change)

DSW7: Additional setting 4. Not used
Factory setting
Defrost for the water electric heater
(Do not change)

DSW8/DSW18: Not used
Factory setting
(Do not change)
11
PMML0603 rev.0 - 02/2023 - 1000014074

DSW15 & RSW2/ DSW16 & RSW1: Not used
Factory setting
(Do not change)

SSW1: Remote/Local
Factory setting
(Do not change)

SSW2: Heat/Cool
Factory setting
(Do not change)
8.5.3 LED indication
Name
Colour
LED1
Green
Power indication
LED2
Red
Power indication
LED3
Red
Heat pump operation (thermo ON/OFF)
LED4
Yellow
Alarm (flickering with 1 sec interval)
LED5
Green
Not used
LED6
Yellow
H-Link transmission
LED7
Yellow
H-Link transmission for unit controller
Remote
Local
Heat
Cool
Indication

Publicidad

loading

Este manual también es adecuado para:

Atw-ymm-02