3. Specifications

3. Specifications
General
Process connection
Materials
Pressure connections
Sealings
Media chamber
Sensor element
Differential pressure measuring
ranges
Max. working pressure (stat.)
Overpressure safe either side
max.
Measurement time constant
Accuracy (error band)
Linearity, hysteresis
Temperature coefficient
Zero offset
Permissible ambient temperature -10 °C ... 50 °C
Permissible medium temperature -10 °C ... 80 °C
Ingress protection

Electrical data

Nominal voltage
Permissible supply voltage
Electrical connection
Output signal
Max. load
Current supply
at output max.
at current limitation
Wiring protection
Electrical connection
3-wire numbered cable
Connection with snap-in M8
connector (3-pin)
WIKA operating instructions differential pressure transmitter model 890.09.2190
2 x 7/16 UNF male thread
Cu alloy - wetted
FPM/FKM - wetted
Zinc diecast - wetted
Ceramic Al
O
- wetted
2
3
0 ... 1 bar, 0 ... 2 bar, 0 ... 4 bar, 0 ... 6 bar or
0 ... 10 bar
21 bar
2.5 x end value of measuring range, max. 21 bar
Pressure spikes are to be reduced through
constructive measures (e.g. capillaries)
T
= 10 ms (sensor + electronics)
mess
± 2 % of span (linearity, hysteresis, temperature
error 10 ... 70 °C)
± 1 % of span
0.2 % of span / 10 K
± 0.1 mA
IP 55 per EN 60529 / IEC 529
DC 24 V
DC 18 ... 30 V
3-wire
4 ... 20 mA
500 Ohm
approx. 32 mA normal (typical)
approx. 36 mA (at overpressure)
Short-circuit-proof, after eliminating the fault the
operability is recovered
0.34 mm², 0.8 m to 2.5 m long
replaceable at the instrument, outer cable end
with single wires for clamping
GB
7