6.1. GRUPEL 545 CONTROLLER
1
2
3
4
5
6
7
1.
AUTO mode indicator
2. Stop alarm indicator
3. Warning alarm indicator
4. Required maintenance indicator
5. Programmable LED indicators
6. TEST mode selection, enables TEST mode activation
7. AUTO mode selection, activates the automatic mode of the generator
8. MAN mode selection, activates the manual mode of the generator
9. STOP selection, allows the generator to stop
10. RUN mode selection, allows the generator to be started manually
11. Generator availability indication
12. Manual opening of the generator circuit-breaker
13. Display of generator circuit breaker status
14. Display of the mains circuit breaker status
15. Manual breaker opening of the mains
16. Mains availability indication
17. Navigation keys
18. Instrumentation screen
Operating mode - TEST
In this mode of operation it is possible to perform a load test, even if the mains is available,
for this it is necessary to press the button 6. The generator will start and reverse automati-
cally, even if the mains is present. In all modes previously described, it is possible to stop the
generator by pressing the button 9.
Operating mode - MANUAL
This operating mode allows the generator to be manually started. It is necessary to press
the button 8 and then the button 10.
Operating mode - AUTOMATIC
In this mode, the generator is started by mains failure or by a remote start signal, automati-
cally without any intervention of the operator. To do this, simply press the button 7.