Descargar Imprimir esta página

Haier YR-E17 Manual De Operación E Instalación página 21

Mando por cable
Ocultar thumbs Ver también para YR-E17:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 115
Operation
Malfunction Display
(1) Under no screen saving state, press 
 key for 10 seconds to check all indoor units malfunction 
in the group. Unit No. is displayed behind the top-left colon; current malfunction is displayed before 
top-right colon and historical malfunction is behind colon.
(2) Unit No. is displayed in decimal and malfunction is displayed in hexadecimal.
(3) All hexadecimal numbers of malfunction are in capital. But b and d is in small capital in order not to 
mix with 8.
(4) If there is no current malfunction, "--" is displayed before the right colon; if there is no historical 
malfunction, "--" is displayed behind the right colon.
(5) Press 
 key to quit malfunction check state. The clock information and timer information are 
displayed.
(6) Malfunction records clearance: Keep pressing 
 key for 10 seconds, malfunction is displayed. 
Then press 
 key again for 5 seconds to clear current and historical malfunction of all the units. 
(7) Press     to choose unit No..
Child Lock
(1) Child lock function can be used to prevent false operation. All of keys are locked after pressing 
and   together for 5 seconds. child lock icon 
 will display on the interface. All of settings will exit 
and keep the previous state. All of keys are invalid including "ON/OFF".
(2) The screen will unlock after pressing 
 and   together for 5 seconds, child lock icon will 
disappear and all keys are available.
Note:
When controlling Fresh Air unit, the controller main interface will not display Up/Down key in normal 
state. When in child lock setting, press Time key first to display Up/Down key at the main interface, 
and then press Set and Down key together for 5 seconds to enter child lock setting. After setting child 
lock, Up/Down key will keep displaying for the convenience of cancellation of child lock.