Technical parameters
Outputs
Output:
Switched voltage:
Switched output:
Peak current:
Output relays separated
from all internal circuits:
Isolation between relay in-
puts COM1, COM2 and COM3:
Isolates. voltage open
relay contact:
Max. current of one
common terminal:
Minimal switched current:
Switching frequency
without load:
Switching frequency with
rated load:
Mechanical life:
Electrical life AC1:
Output indication:
Communication
Installation BUS:
The installation BUS is sepa-
rated from all internal circuits:
Status indication unit:
Power supply
Voltage of BUS / tolerance /
nominal current:
Supply voltage of power
section (relay) tolerance /
nominal current:
Dissipated power:
Connection
Terminal:
Operating conditions
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operation position:
Installation:
Design:
Dimensions and weight
Dimensions:
Weight:
TECHNICAL SUPPORT | E-mail: support@inels.com | Mobil: +420 778 427 366 | Tel.: +420 573 514 276, +420 573 514 211 | Fax: +420 573 514 227 | www.inels.com
Made in Czech Republic
SA3-012M
SA3-012M/120V
12x NO 8 A/AC1
250 V AC, 24 V DC
2000 VA/AC1, 192 W/DC
10 A
reinforced Insulation
(Cat. II surges by EN 60664-1)
reinforced Insulation
(Cat. II surges by EN 60664-1)
1 kV
16 A
100 mA / 10 V DC
-1
300 min
-1
15 min
1x 10
7
5
1x 10
12x yellow LED
BUS
reinforced Insulation
(Cat. II surges by EN 60664-1)
green LED RUN
27 V DC, -20 / +10 %, 5 mA
AC 230 V (50 Hz),
AC 120 V (60 Hz),
-15 / +10 %, 20 mA
-15 / +10 %, 40 mA
max. 6 W
max. 5 W
2
2
max. 2.5 mm
/ 1.5 mm
with sleeve
-20 .. +55 °C
-30 .. +70 °C
IP20 device, IP40 mounting in the switchboard
II.
2
any
switchboard on DIN rail EN 60715
6-MODUL
90 x 105 x 65 mm
310 g
ELKO EP, s.r.o. | Palackého 493 | 769 01 Holešov, Všetuly | Czech republic | e-mail: elko@elkoep.com
Warning
Before the device is installed and operated, read this instruction manual carefully and with full
understanding and Installation Guide System iNELS3. The instruction manual is designated for
mounting the device and for the user of such device. It has to be attached to electro-installation
documentation. The instruction manual can be also found on a web site www.inels.com. Attention,
danger of injury by electrical current! Mounting and connection can be done only by a professional
with an adequate electrical qualifi cation, and all has to be done while observing valid regulations.
Do not touch parts of the device that are energized. Danger of life-threat! While mounting,
servicing, executing any changes, and repairing it is essential to observe safety regulations, norms,
directives and special regulations for working with electrical equipment. Before you start working
with the device, it is essential to have all wires, connected parts, and terminals de-energized. This
instruction manual contains only general directions which need to be applied in a particular
installation. In the course of inspections and maintenance, always check (while de-energized) if
terminals are tightened.