16
en | Specifications
General
Operating voltage (SLC loop)
Maximum current consumption at 77 °F (25 °C) and
39 V bus voltage
–
Standby
–
Alarm
–
When polled
Maximum allowable line resistance
Installation temperature
Storage temperature
–
Without CO sensor
–
With CO sensor
Humidity
Protection category
Mounting locations and heights in general
Maximum spacing between detectors
–
Smoke detector
–
Heat detector
Minimum mounting distance to magnets
(e.g. loudspeaker)
Maximum wiring length to C point
Dimensions (diameter x height)
–
Detector
–
Detector with 4-inch base
–
Detector with 6-inch base
Housing material
Table 8.1 Technical Specifications
Sensors
Maximum airflow
Sensitivity
–
Smoke sensor
–
Heat sensor (FAP-440 detectors)
–
Heat sensor (FAH-440 heat detectors)
Table 8.2 Technical Specifications Sensors
Isolator Bases
Maximum current consumption at 77 °F (25 °C) and
39 V bus voltage
–
Standby
–
Alarm
Internal resistance
Power up time
Shut down
Table 8.3 Technical Specifications Isolator Bases
F.01U.173.498 | 1.3 | 2012.02
24 V DC to 41 V DC
170 μA
5 mA
22 mA ± 20%
50 Ω
+32 °F to +100 °F (0 °C to +38 °C)
If the sensitivity temperature is programmed within a range of
+175 °F to +249 °F (+79.4 °C to +120.6 °C), the maximum
installation temperature is +150 °F (+66 °C).
-13 °F to +176 °F (-25 °C to +80 °C)
+14 °F to +122 °F (-10 °C to +50 °C)
< 95% (non-condensing)
IP 42
Refer to NFPA-72
30 ft. (9.1 m)
50 ft. (15.2 m)
11.8 in. (30 cm)
9.8 ft. (3 m)
4.4 in. x 2.0 in. (11.2 cm x 5.1 cm)
5.0 in. x 2.5 in. (12.7 cm x 6.4 cm)
7.0 in. x 2.5 in. (17.8 cm x 6.4 cm)
Cycoloy/ABS
4000 ft/min (20m/s)
1.25%/ft to 3.5%/ft
+135 °F (+57 °C) + RoR
+135 °F to +194 °F (+57 °C to +90 °C), programmable + RoR
70 μA
10 mA
< 50 mΩ
< 30 ms
< 50 ms
Installation and Operation Guide
Analog Detectors and Bases
Bosch Security Systems, Inc.